Maintenance, Problems with the controller, Calibration of the input – NOVUS Controller N1200 User Manual

Page 11: Analog output calibration, Serial communication

Advertising
background image

Controller N1200

NOVUS AUTOMATION

11 / 13

The methods of automatic tuning and auto-adaptative tuning are

appropriate for most of the industrial processes. However, there may

be processes or even specific situations where the methods are not

capable to determine the controller's parameters in a satisfactory

way, resulting in undesired oscillations or even taking the process to

extreme conditions. The oscillations themselves imposed by the

tuning methods may be intolerable for certain processes. These

possible undesirable effects must be considered before beginning

the controller's use, and preventive measures must be adopted in

order to assure the integrity of the process and users.
The “TUNE” signaling device will stay on during the tuning process.
In the case of PWM or pulse output, the quality of tuning will also

depend on the cycle time adjusted previously by the user.
If the tuning does not result in a satisfactory control, refer to Table 8

for guidelines on how to correct the behavior of the process.

PARAMETER

VERIFIED PROBLEM

SOLUTION

Proportional Band

Slow answer

Decrease

Great oscillation

Increase

Rate of Integration

Slow answer

Increase

Great oscillation

Decrease

Derivative Time

Slow answer or instability

Decrease

Great oscillation

Increase

Table 8 - Guidance for manual adjustment of the PID parameters

MAINTENANCE

PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most

common errors found during the controller operation. A final revision

may avoid loss of time and damages.
The controller displays some messages to help the user identify

problems.

MESSAGE

DESCRIPTION OF THE PROBLEM

----

Open input. No sensor or signal.

Err1

Err6

Connection and/or configuration errors. Check

the wiring and the configuration.

Other error messages may indicate hardware problems requiring

maintenance service. When contacting the manufacturer, inform the

instrument serial number, obtained by pressing the key

for more

than 3 seconds.

CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done

by qualified personnel. If you are not familiar with these procedures

do not attempt to calibrate this instrument.
The calibration steps are:
a) Configure the type of input to be calibrated.
b) Configure the lower and upper limits of indication for the

maximum span of the selected input type.

c) At the input terminals inject a signal corresponding to a known

indication value a little above the lower display limit.

d) Access the parameter “inLC”. With the keys

and

adjust the

display reading such as to match the applied signal. Then press the

P

key.

e) Inject a signal that corresponds to a value a little lower than the

upper limit of indication.

f) Access the parameter “inLC”. With the keys

and

adjust

the display reading such as to match the applied signal. Then

press the

P

key.

Note: When checking the controller calibration with a Pt100

simulator, pay attention to the simulator minimum excitation current

requirement, which may not be compatible with the 0.170 mA

excitation current provided by the controller.

ANALOG OUTPUT CALIBRATION
• Configure I/O 5 for the current output to be calibrated, be it

control or retransmission.

• In the screen “Ctrl”, program manual mode (

man

).

• Connect a current meter to the analog output.
• Enter the calibration cycle with the correct password.
• Select the screen “ovLC”. Press the keys

and

for the

controller to recognize the calibration process of the current

output.

• Read the current indicated on the current meter and adjust the

parameter “ovLC” to indicate this current value (use the keys

and

)

• Select the screen “ovxC”. Press the keys

and

for the

controller to recognize the calibration process of the current

output.

• Read the current indicated on the current meter and adjust the

parameter “

ovkC

” to indicate this current value

• Press the key

P

in order to confirm the calibration procedure

and return to the operating level.

SERIAL COMMUNICATION

The controller can be supplied with an asynchronous RS-485 digital

communication interface for master-slave connection to a host

computer (master).
The controller works as a slave only and all commands are started by

the computer which sends a request to the slave address. The

addressed unit sends back the requested reply.
Broadcast commands (addressed to all indicator units in a multidrop

network) are accepted but no reply is sent back in this case.

CHARACTERISTICS
• Signals compatible with RS-485 standard. MODBUS (RTU)

Protocol. Two wire connection between 1 master and up to 31

(addressing up to 247 possible) instruments in bus topology. The

communication signals are electrically insulated from the rest of

the device;

• Maximum connection distance: 1000 meters.
• Time of disconnection for the controller: Maximum 2 ms after last

byte.

• Selectable speed; 8 data bits; 1 stop bit; selectable parity (no

parity, pair or odd);

• Time at the beginning of response transmission: maximum 100

ms after receiving the command.

The RS-485 signals are:

D1 D D + B Bi-directional data line.

Terminal 16

D0

D - A Bi-directional inverted data line.

Terminal 17

C

Optional connection that improves the

performance of the communication.

Terminal 18

GND

CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION
Two parameters must be configured for using the serial type:
bavd:

Communication speed.

prty:

Parity of the communication.

addr:

Communication address for the controller.







D:

Advertising