Controller N3000

NOVUS AUTOMATION

6/9

CONFIGURATION CYCLE

type

INPUT TYPE: Selects the input signal type to be

connected to the process variable input. Refer to

Table 1.
This is the first parameter to be set.

dppo

DECIMAL POINT POSITION: For input types 16, 17,

18 or 19 only. Selects the decimal point position to be

viewed in both PV and SV.

vnIt

TEMPERATURE INDICATION IN ºC OR ºF: Selects

the display indication to be in ºC or ºF. Only available

if input type is other than 16, 17, 18 or 19.

offs

SENSOR OFFSET: Offset value to be added to the

PV to compensate sensor error. Default value: zero.

spll

SET POINT LOW LIMIT:
- Linear inputs: Sets the lower range for SV and PV

indication.
- T/C and Pt100 inputs: sets the lower range for SV.

spxl

SET POINT HIGH LIMIT:
- Linear inputs: Sets the upper range for SV and PV

indication.
- T/C and Pt100 inputs: sets the upper range for SV.

rsll

REMOTE SET POINT LOW LIMIT: Selects the lower

range for indication of the Remote Setpoint.

rsxl

REMOTE SET POINT HIGH LIMIT: Selects the upper

range for indication of the Remote Setpoint.

bavd

DIGITAL COMMUNICATON BAUD RATE

SELECTION:

0: 1200bps; 1: 2400bps; 2: 4800bps; 3: 9600bps; 4:

19200bps.

addr

SLAVE ADDRESS SELECTION: Identifies a slave in

the network. The possible address numbers are from 1

to 247.

I/O CYCLE (INPUTS AND OUTPUTS)

Io 1

I/O 1 FUNCTION: Selects the I/O function to be used

at I/O 1 (relay 1). Options 0 to 5 are possible for this

output. It is normally used as option 5, PWM main

control output. Refer to Table 2 for functions.

Io 2

I/O 2 FUNCTION: Selects the I/O function to be used

at I/O 2 (relay 2). Options 0 to 5 are available. This

output is normally used as alarm output. See Table 2

for functions.

Io 3

I/O 3 FUNCTION: Selects the I/O function to be used

at I/O 3 (option 1). I/O 3 can be a relay output or a

digital input/output. Functions 0 to 10 are available.

Refer to Table 2 for functions. The presence of this I/O

option is detected by the controller and the prompt

menu will only be shown if the expansion option is

available.

Io 4

I/O 4 FUNCTION: Selects the I/O function to be used

at I/O 4 (option 2). I/O 4 can be a digital input/output.

Functions 0 to 10 are available. Refer to Table 2 for

functions. The prompt menu will only be shown if the

expansion option is present.

Io 5

I/O 5 FUNCTION: Selects the I/O function to be used

at I/O 5 (Analog Output). Functions 0 to 15 are

available (See Table 2). This option is normally used

for main control output or PV analog retransmission.

I o 6

I/O 6 FUNCTION: Selects the I/O function to be used

at I/O 6 (Digital Input). Options 0, 6, 7, 8, 9 and 10 are

possible for this input. Refer to Table 2 for functions.

f.fvnc

F KEY FUNCTION: Selects the I/O function assigned

to the front panel

key. Available functions are:

0

- Key not used;

7

- Start/Stop the controller (RUN function);

8

- Select remote setpoint;

9

- Execute/Hold ramp and soak profile;

10

- Enable/Disable ramp and soak profile 1;

Details on these functions are described in section 5.2.

Figure 7 shows the sequence of cycles and parameters presented in

the indicator display. There are parameters that must be defined for

each alarm available.

Operation

Cycle

Auto

Tuning

Cycle

Programming

Cycle

Alarm

Cycle

Configuration

Cycle

I/Os

Cycle

PV e SP atvn Tbas

fva1 -

fva4

type

io1

avto

pb

pr n

bla1 -

bla4

dppo

io2

PV e MV hyst Ptol

kya1 -

kya4

vnit

io3

pr n

ir

psp0 -

psp7

A1t1

offs

Io4

rvn

dt

pt1 -

pt7

a1t2

spll

Io5

(t

pe1 -

pe7

a2t1

spkl

Io6

a(t

Lp

a2t2

rsll

f.fvnc

bias

Rskl

Figure 10 - Sequence of cycles and parameters presented in the controller display

CALIBRATION CYCLE
All input and output types are factory calibrated. This cycle should

only be accessed by experienced personnel. If in doubt do not press

the

or

keys in this cycle.

Inl(

INPUT LOW CALIBRATION: Sets the Process

Variable low calibration (offset). Several keystrokes at

or

might be necessary to increment one

digit.

Inx(

INPUT HIGH CALIBRATION: Sets the Process

Variable span calibration (gain).

ovll

OUTPUT LOW CALIBRATION: Sets the analog

current output low calibration (offset).

Ovx(

OUTPUT HIGH CALIBRATION: Sets the analog

current output span calibration (gain).

(j l

COLD JUNCTION OFFSET CALIBRATION: Sets the

cold junction offset calibration.

xtyp

HARDWARE TYPE: Configures the controller to

recognize the actual installed optional hardware

(accessories). The parameters menu will show the

parameters relative to the optional hardware:
0 - no optionals or c/ RS485 only;
1 - relay 3 (I/O 3);
2 - Digital I/O (2 inputs/outputs: I/O3 and I/O4);
3 - Heater break protection (option);

Rsl(

REMOTE SET POINT LOW CALIBRATION: Sets the

Remote Set Point low calibration (offset). Several

keystrokes at

or

might be necessary to

increment one digit.

Rsx(

REMOTE SET POINT HIGH CALIBRATION: Sets the

Remote Set Point span calibration (gain).