10 SERIAL COMMUNICATION

The indicator can be supplied with an asynchronous RS-485 digital communication interface for
master-slave connection to a host computer (master).

The indicator works as a slave only and all commands are started by the computer which sends a
request to the slave address. The addressed unit processes the command and sends back the
answer.

Broadcast commands (addressed to all indicator units in a multidrop network) are accepted but no
response is generated.

CHARACTERISTICS

- RS-485 compatibility with two-wire bus from the host to up to 31 slaves in a multidrop network

topology.

- Up to 247 units can be addressed by the MODBUS RTU protocol.

- Maximum network distance: 1200 m.

- Time of indicator disconnection: Maximum of 2 ms after the delivery of the last byte.

- Communication signals electrically isolated from the rest of the instrument.

- Baud rate: 1200, 2400, 4800, 9600, 19200, 38400 or 57600 bps.

- Number of data bits: 8, without parity or even parity

- Number of stop bits: 1

- Time to start response transmission: 100 ms maximum delay after acknowledging the command.

- Protocol: MODBUS (RTU)

10.1 RS485 INTERFACE: ELECTRICAL CONNECTION

The RS-485 signals are:

D1 = D:

Bidirectional data line

D0 = D: Inverted bidirectional data line
C = GND: Optional connection. Improves communication performance for

long cable runs.

COMMUNICATION PARAMETERS CONFIGURATION

Two parameters must be configured for serial use:

bavd:

Communication speed. All equipments with the same speed.

Adres: Controller communication address. Each controller must have an exclusive address.