NOVUS N321 User Manual

Page 2

Advertising
background image

Level 3 – Calibration level
The controller is factory calibrated. The following parameters should be accessed
only by experienced personnel. To enter this cycle, the

key must be kept

pressed for 4 seconds.
Don’t press the

and

keys if you are not sure of the calibration

procedures. Just press the

key a few times until the temperature

measurement level is reached again.

pas

Password - Enter the correct password to unlock write

operations for the parameters in the following levels.

[Al

Calibration low - Offset value of the input. It adjusts the lower

measurement range of the sensor.

[Ak

Calibration High - Gain calibration. It adjusts the upper

measurement range of the sensor.

[JL

Cold Junction Offset calibration - This parameter is available

only for thermocouple.

FA(

Factory

Calibration

-

Restores

factory

calibration

parameters. Change from 0 to 1 to restore the calibration
parameters with factory values.

Prt

Protection - Defines the levels of parameters that will be

password protected. See "Configuration Protection" for details.

Pa(

Password Change - Allows changing the current password to a

new one. Values from 1 to 999 are allowed.

Sn2

Serial number - First part of the controller electronic serial number.

sn1

Serial number - Second part of the controller electronic serial

number.

sn0

Serial number - Third part of the controller electronic serial number.

WORKING WITH THE CONTROLLER

The N321 energizes the output relay such as to maintain the process temperature

on the setpoint value defined by the user. The output status led P1 signals when
the control output is on.

DISPLAY

OUTPUT STATUS LED

KEYBOARD

Fig. 2 – Frontal Panel

CONFIGURATION PROTECTION

A protection system to avoid unwanted changes to the controller parameters
is implemented. The level of protection can be selected from partial to full. The

following parameters are part of the protection system:
Pas

When this parameter is presented, the correct password should be entered

to allow changes of parameters in the following levels.

Prt

Defines the level of parameters that will be password protected:

1 - Only calibration level is protected (factory configuration);
2 - Calibration and Configuration levels are protected;
3 - All levels are protected - calibration, Configuration and setpoints.

PA(

Parameter for definition of a new password. Since it is located in the

calibration level, can only be changed by a user that knows the current
password. Valid passwords are in the range 1 to 999.

Configuration protection usage
PAS

parameter is displayed before entering a protected level. If the correct

password is entered, parameters in all following levels can be changed. If wrong
or no password is entered, parameters in the following levels will be read only.
Important notes:
1- After five consecutive attempts to enter a wrong password, new tentative will be

blocked for the next 10 minutes. If the current valid password is unknown, the

master password can be used only to define a new password for the controller.

2 - The password for a brand new device is 111.

MASTER PASSWORD

The master password allows user to define a new password for the controller,
even if the current password is unknown. The master password is based in the

serial number of the controller, and calculated as following:

[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]

for example the master password for the device with serial number 987123465 is:
1 9 3 6

as follows: 1 + sn2= 987; sn1= 123; sn0= 465 = 1 + 9 + 3 + 6

How to use the master password:
1- Enter the master password value at PaSprompt.
2- Go to PA( parameter and enter the new password, which must not be zero (0).
3- Now you can use this new password to access all controller parameters with

modify rights.

ERROR MESSAGES

Sensor measurement errors force the controller outputs to be turned off. The
cause for these errors may have origin in a bad connection, sensor defect (cable

or element) or system temperature outside the sensor working range. The display
signs related to measurement errors are shown below:

Measured temperature exceeded maximum allowed range for

the sensor. Broken Pt1000 or T/C. Short circuited NTC sensor.

Measured temperature is below minimum measurement range of

the sensor. Short circuited Pt1000 or T/C. Broken NTC.

ELECTRICAL WIRING

It is important to follow the recommendations below:

Signal wires should be installed in grounded conduits and away from power or

contactor wires.

The instrument should have its own power supply wires that should not be

shared with electrical motors, coils, contactors, etc.

Installing RC filters (47 R and 100 nF, series combination) is strongly

recommended at contactor coils or any other inductors.

System failure should always be taken into account when designing a control

panel to avoid irreversible damage to equipment or people.

WARRANTY

Warranty conditions are available on our web site

www.novusautomation.com

.