ALARM FUNCTION DESCRIPTION

Minimum and maximum alarms are used to signal extreme
temperature values. Such extreme values are defined in the “aisp”
and “a2sp”. Differential alarms are used to signal deviations between
the temperature and the control setpoint (SP). User-defined values in
the “aisp” and “a2sp” parameters represent the values of such
deviations.
The initial blocking prevents the alarm from being triggered when the
controller is turned on until the temperature reaches the SP value for
the first time.
The error alarm in the sensor signals sensor faults.
Table 2 shows the operation of each alarm function, using alarm 1 as
an example, and presents its identification code in the “aifv” and
“a2fv” parameters.

TYPE

PROMPT

ACTION

Disabled

Off

Alarm disabled

Open Sensor

(input Error)

Ierr

Triggered when the sensor is

broken

Minimum

value

(Low)

Lo

A1SP

PV

OFF

ON

Maximum

value (High)

Ki

A1SP

PV

Minimum

differential

(Differential

Low)

Dif.lo

PV

SP

SP

– A1SP

Maximum

differential

(Differential

High)

Dif.ki

PV

SP + A1SP

SP

Out of range

differential

(Differential

Out)

Dif.ov

PV

SP + A1SP

SP

SP

– A1SP

Differential

within range

(Differential

In)

Dif.In

PV

SP + A1SP

SP

SP

– A1SP

Table 2 – Alarm functions and identification codes

PID PARAMETERS AUTO-TUNE

One of the major doubts users have is to know which values to adopt
in PID parameters for a more effective control of the process. The
Auto-tune (Atvn) is the controller resource that determines such
values automatically.
When the Auto-tune is enabled, the controller will control the process
temperature and identify its characteristics, calculating the best
values for the PID parameters. During auto-tune the process is
controlled in the ON/OFF mode in the programmed value of the
setpoint. Depending on the process features, great temperature
oscillations may occur, above and below the SP value. The user must
check if the process supports such oscillations. Auto-tune can take
several minutes to conclude in some processes.
In the controller front panel, the signal TUNE lights when auto-tuning
is being performed. At the end of the process, the signal disappears.
For other SP values, other PID parameters may be required. The
recommended procedure is the following:

Program SP as a value close to the value in which the process will
operate after tuned.

Enable the auto-tune in the “atvn” prompt by selecting 1.

Program 1 in the “rvn” prompt.

If auto-tune does not result a satisfactory control, Table 3 shows
actions that will adjust the process behavior.

PARAMETER

PROBLEM

SOLUTION

Proportional band

Slow response

Decrease

Large oscillation

Increase

Integration rate

Slow response

Increase

Large oscillation

Decrease

Derivative time

Slow response or

instability

Decrease

Large oscillation

Increase

Table 3 – Orientation for the manual adjustment of the PID parameters

SAFETY INFORMATION

This product is not a protection or safety device and its alarms are not
intended to protect against product failures. Independent safety devices
should be always provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.

SUPPORT AND MAINTENANCE

This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service. For troubleshooting,
visit our FAQ at www.novusautomation.com.

LIMITED WARRANTY AND LIMITATION OF
LIABILITY

NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) year from the date of shipment from factory or
from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the
cost of correcting defects in the product or of supplying replacement
product as herein provided and upon the expiration of the warranty
period all such liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our web site: www.novusautomation.com.

Advertising