NOVUS N321S User Manual
Page 2

Ky2
Ky2
Ky2
Ky2
Histeresis 2
Overheating temperature hysteresis of sensor S2 (kt2
kt2
kt2
kt2). In
degrees.
Adjustable between 0.1 and 50.0 °C.
dly
dly
dly
dly
Delay
Control start delay. After having the controller turned on, the
control output will be activated after the time programmed in this
parameter has lapsed.
Value in seconds, from 0 to 250 seconds.
0f1
0f1
0f1
0f1
Offset Sensor 1
Offset correction value for the temperature measured by the
sensor 1. This parameter allows for small adjustments in the
sensor 1 temperature reading. Measurement differences may
happen, for instance, when a temperature sensor is replaced.
Adjustable from -10.0 to 10.0 °C.
0f2
0f2
0f2
0f2
Offset Sensor 2
Offset correction value for the temperature measured by the
sensor 2. This parameter allows small adjustments to the sensor
2 temperature reading. Measurement differences may occur, for
instance, when a temperature sensor is replaced.
Adjustable from -10.0 to 10.0 °C.
sp
sp
sp
spl
l
l
l
SP Low Limit
Lower limit of the setpoint value: defines the minimum value for
setpoint adjustment. In degrees.
Adjustable between -50 and 120 °C.
spk
spk
spk
spk
SP High Limit
Upper limit of the setpoint: defines the maximum value for
setpoint adjustment. Must be defined with a value necessarily
higher than spl
spl
spl
spl. In degrees.
Adjustable between -50 and 120 °C.
Add
Add
Add
Add
Address
Modbus Address: used to define a unique network address in
instruments that are featured with the optional RS485 Modbus
RTU communication.
Address range is from 1 to 247.
Nível 3 – Calibration level
The N321S inputs are factory calibrated and recalibration should only be done by
qualified personnel. If you are not familiar with these procedures do not attempt to
calibrate this.
Press the
key for 10 seconds to access this level. This level contains also the
parameters for configurating the protection.
If you have entered this level accidentally, go through all the parameters without
making any changes until the controller returns to the measurement level.
pas
pas
pas
pas
Password - Enter the correct password to unlock write operations in
the following parameters.
[
[
[
[l
l
l
l1
1
1
1
Calibration Low Input 1 – Input 1 offset.
[
[
[
[k
k
k
k1
1
1
1
Calibration High Input 1 – Gain adjustment (full scale value).
[l2
[l2
[l2
[l2
Calibration Low Input 2 - Input 2 offset.
[k2
[k2
[k2
[k2
Calibration High Input 2 – Input 2 gain adjustment (full scale value).
FA(
FA(
FA(
FA(
Factory Calibration - Restores factory calibration parameters.
Change from 0 to 1 to restore the calibration parameters with factory
values.
Prt
Prt
Prt
Prt
Protection - Defines the levels of parameters that will be password
protected. See "Configuration Protection" for details.
Pa(
Pa(
Pa(
Pa(
Password Change - Allows changing the current password to a
new one. Values from 1 to 999 are allowed.
Sn2
Sn2
Sn2
Sn2
Serial number 2 - First part of the controller electronic serial number.
sn1
sn1
sn1
sn1
Serial number 1 - Second part of the controller electronic serial
number.
sn0
sn0
sn0
sn0
Serial number 0 - Third part of the controller electronic serial
number.
WORKING WITH THE CONTROLLER
While the solar collector is receiving energy, the temperature in the sensor S1
increases. When T1 – T2 is higher than the value specified in d0n
d0n
d0n
d0n, the pump will
be turned on, circulating the heated water down and storing it in the tank.
As the pump is operating, the hot water will circulate downwards and the cold water
goes upwards. Consequently, the temperature difference between S1 and S2 tends
to diminish. When this difference goes under the value configured in d0f
d0f
d0f
d0f, the
pump will be turned off and the water circulation will stop.
The signaler P1 at the front panel of the controller will light up when the control
output is activated.
Figure 2 – Front Panel
Indicator
Function
T1
Sensor 1 temperature
T2
Sensor 2 temperature
T1 T2
S1 – S2 (Differential Temperature)
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters is
implemented. The level of protection can be selected from partial to full. The
following parameters are part of the protection system:
Pa
Pa
Pa
Pas
s
s
s:
When this parameter is presented, the correct password should be
entered to allow changes of parameters in the following levels.
Prt
Prt
Prt
Prt:
Defines the level of parameters that will be password protected:
1 - Only calibration level is protected (factory configuration);
2 - Calibration and configuration levels are protected;
3 – All levels are protected – calibration, configuration and setpoints;
PA(
PA(
PA(
PA(
Parameter for definition of a new password. Since it is located in the
calibration level, can only be changed by a user that knows the current
password. Valid passwords are in the change 1 to 999.
CONFIGURATION PROTECTION USAGE
PAS
PAS
PAS
PAS parameter is displayed before entering a protected level. If the correct
password is entered, parameters in all following levels can be changed. If wrong or
no password is entered, parameters in the following levels will be read only.
Important notes:
1 - After five consecutive attempts to enter a wrong password, new tentative will be
blocked for the next 10 minutes. If the current valid password is unknown, the
master password can be used only to define a new password for the controller.
2 - The password for a brand new device is 111.
MASTER PASSWORD
The master password allows user to define a new password for the controller, even
if the current password is unknown. The master password is based in the serial
number of the controller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]
For example the master password for the device with serial number 987123465 is: 1936
As follows:
sn2
sn2
sn2
sn2= 987;
sn1
sn1
sn1
sn1= 123;
sn0
sn0
sn0
sn0= 465 =
1 + 9 + 3 + 6
How to use the master password:
1- Enter the master password value at PaS
PaS
PaS
PaS prompt.
2- Go to PA(
PA(
PA(
PA( parameter and enter the new password, which must not be zero (0).
3- Now you can use this new password to access all controller parameters with
modify rights.
ERROR MESSAGES
Sensor measurement errors force the controller outputs to be turned off. The cause
for these errors may have origin in a bad connection, sensor defect (cable or element)
or system temperature outside the sensor working range. The display signs related to
measurement errors are shown below:
•
Measured temperature exceeded maximum allowed
range for the sensor. Short circuited NTC sensor.
I
I
I
IND
ND
ND
ND = 0
0
0
0 or 1
1
1
1
•
Measured temperature is below minimum measurement
range of the sensor. Broken NTC.
IND
IND
IND
IND = 0
0
0
0 or 1
1
1
1
•
If the temperature in S1 or S2 exceeds the measurement
limit IND
IND
IND
IND = 2
2
2
2, the differential value displayed is 0
0
0
0.
DESIGNATION SYSTEM
N321S
-485
- 24V
A
B
C