NOVUS N1500G User Manual

Page 5

Advertising
background image

Indicator N1500G

NOVUS AUTOMATION

5/5

Dois parâmetros devem ser configurados para utilização da interface
de comunicação serial: o Baud-Rate de Comunicação (parâmetro
bavd

bavd

bavd

bavd) e o Endereço de Comunicação (parâmetro adres

adres

adres

adres).

RS485 INTERFACE: ELECTRICAL CONNECTION

The RS-485 signals are: D1 = D: Bidirectional data line

D0 =

D:

Inverted bidirectional data line

C = GND: Optional connection. Improves

communication performance for
long cable runs.

9.

PROBLEMS WITH THE INDICATOR

Connection errors or improper configuration will result in
malfunctioning of the indicator. Carefully revise all cable connections
and programming parameters before operating the unit.

Some error messages will help the user identify possible problems.

Message

Possible Problem

Measured value is above the programmed
sensor or input signal limit.

Measured value is below the programmed sensor
or input signal limit.

Open input. No sensor is connected or the
sensor is broken.

Pt100 cable resistance is too high or the sensor
is badly connected.

Different messages other than the ones above should be reported to
the manufacturer. Please inform the serial number if this should
occur. the serial number can be viewed at the display by pressing the
BACK key for about 3 seconds.

The software version of the instrument can be viewed at the time the
unit is powered. The instrument might display false error messages
when wrongly programmed or when connected to a sensor for which
it was not programmed.

10.

SPECIFICATIONS

DIMENSIONS:.........................310 x 110 x 37 mm. Approximate weight: 975 g

POWER: .................................................... 100 to 240 Vac/dc ±10 %; 50/60 Hz

Max. Consumption:........................................................................... 10 VA

ENVIRONMENTAL CONDITIONS:

Operating temperature:.............................................................. 5 to 50

°

C

Maximum RH: ........................................................................80 % up to 30 ºC.

.................................. For temperatures above 30 ºC, decrease 3 % per ºC.
........................................................ for indoor use; Installation category II,

pollution degree 2; altitude < 2000 m

INPUT ................................... Keyboard selection of input type (refer to table 1)

Internal resolution: ............................................................... 19500 levels
Display resolution:...........................................................................12000
Input sample rate:.................................................................5 per second
Accuracy: .....................Thermocouples J, K, T, N: 0.25 % of span

±

1 ºC

........................................Thermocouple E, R, S, B: 0.25 % of span

±

3 ºC

................................................................................... Pt100: 0.2 % of span
................................................. 4-20 mA, 0-50 mV, 0-5 V: 0.15 % of span.

Input impedance: ..............0-50 mV, Pt100 and thermocouples: >10 M

...............................................................................................0-5 V: >1 M

.............................................................................0-20 mA, 4-20 mA: 22

Pt100 measurement:............................DIN 43760 standard (

α

=0.00385)

Excitation current: ..................................................................... 0.750 mA

3-wire circuit, cable resistance compensation

ANALOG OUTPUT: ...0-20 mA or 4-20 mA, 550

max.; 4000 levels, isolated

RELAY OUTPUT:....... ALM1 and ALM2: SPST: 1.5 A / 240 Vac (3 A / 30 Vdc)
EMC :............................................ EN 61326-1:1997 and EN 61326-1/A1:1998

SAFETY:......................................... EN61010-1:1993 and EN61010-1/A2:1995

START UP 3 SECONDS AFTER POWER UP;

PROTECTION: IP30

11.

ORDERING INFORMATION

N1500G-

RT -

485

A

B

C

A: Series model:

1500G

B: Analog output:

RT – (Retransmission of the input
signal) or Blank

C:Digital Communication:

485 – ( RS485, ModBus protocol)
or Blanck

12.

WARRANTY

This product is covered by a 12-month warranty provided the
purchaser presents the sales receipt and the following conditions are
met:

Products are covered for one year from the original date of
purchase. Please retain the dated sales receipt as evidence of
the date of purchase. You will need it for any warranty service

Within this period, warranty against defects in material and
workmanship under normal use is free of charge.

For repair, send the product and the sales receipt to our address.
Expenses and transportation risks are under the purchaser’s
responsibility.

This warranty does not cover any damage due to accident,
misuse, abuse, or negligence.

Advertising