NOVUS N1200 User Manual

Page 9

Advertising
background image

9

Register

Value format

Status Word 1

bit 0 – Alarm 1 (0-inactive; 1-active)
bit 1 – Alarm 2 (0-inactive; 1-active)
bit 2 – Alarm 3 (0-inactive; 1-active)
bit 3 – Alarm 4 (0-inactive; 1-active)
bit 4 – Input 0 – I/O 5 (0- inactive; 1- active)
bit 5 – Input 1 – I/O 3 (0- inactive; 1- active)
bit 6 – Input 2 – I/O 4 (0- inactive; 1- active)
bit 7 – Reserved
bit 8 – Hardware detection value
bit 9 – Hardware detection value
bit 10 – Reserved
bit 11 – Reserved
bit 12 – Reserved
bit 13 – Reserved
bit 14 – Reserved
bit 15 – Reserved

Status Word 2

bit 0 – Automatic (0- manual; 1- automatic)
bit 1 – Run (0-stop; 1-run)
bit 2 – Control Action (0-direct; 1-reverse)
bit 3 – Reserved
bit 4 – Auto-tune (0-no; 1-yes)
bit 5 – Alarm 1 power-up inhibit (0-no; 1-yes)
bit 6 – Alarm 2 power-up inhibit (0-no; 1-yes)
bit 7 – Alarm 3 power-up inhibit (0-no; 1-yes)
bit 8 – Alarm 4 power-up inhibit (0-no; 1-yes)
bit 9 – Unit (0-°C; 1-°F)
bit 10 – Reserved
bit 11 – Output 1 status
bit 12 – Output 2 status
bit 13 – Output 3 status
bit 14 – Output 4 status
bit 15 – Output 5 status

Status Word 3

bit 0 – Very low PV conversion (0-no; 1-yes)
bit 1 – Negative conversion after calibration (0-no; 1-yes)
bit 2 – Very high PV conversion (0-no; 1-yes)
bit 3 – Exceeded linearization limit (0-no; 1-yes)
bit 4 – Very high Pt100 cable resistance (0-no; 1-yes)
bit 5 – Self zero conversion out of range (0-no; 1-yes)
bit 6 – Self span conversion out of range (0-no; 1-yes)
bit 7 – Reserved
bit 8 – Reserved
bit 9 – Reserved
bit 10 – Reserved
bit 11 – Reserved
bit 12 – Reserved
bit 13 – Reserved
bit 14 – Reserved
bit 15 – Reserved

Table 2: Values of Status Words


Writing to an output bit is only possible if the output has no function assigned to it
(the output is configured to OFF in Alarm Cycle).

Coil Status

Output description

1

Output 1 Status (I/O1)

2

Output 2 Status (I/O2)

3

Output 3 Status (I/O3)

4

Output 4 Status (I/O4)

5

Output 5 Status (I/O5)

Exception Responses – Error Conditions

The MODBUS RTU protocol checks the CRC in the data blocks received.

Reception errors are detected by the CRC, causing the controller to discard the
packet, not sending any reply to the master.

After receiving an error-free packet, the controller processes the packet and verifies
whether the request is valid or not, sending back an exception error code in case of
an invalid request. Response frames containing error codes have the most
significant bit of the Modbus command set.

If a WRITE command sends an out-of-range value to a parameter, the controller will
clamp the value to the parameter range limits, replying with a value that reflects
these limits (maximum or minimum value allowed for the parameter).

The controller ignores broadcast READ commands; the controller processes only
broadcast WRITE commands.

Error Code

Error Description

01

Invalid Command

02

Invalid Register Number or out of range

03

Invalid Register Quantity or out of range

Table 3 – Exception response error codes

Advertising