Tables for data interchange

Reading Table:

Figure 8 – Reading of the Modbus slaves by the Profibus master

The Reading Table or Input Table contains the values read of the Modbus network equipment registers (according to
the equipment configuration), besides a status register (1st position of the table). The table corresponds to the field of
data sent from the DigiGate to the Profibus master. Its format is as follows:

Position 0

Status Register – in details as follows

Position 1

Register value of the equipment in the Modbus network

Position 2

Register value of the equipment in the Modbus network

.................

.......................................................................................................

Position 121

Register value of the equipment in the Modbus network

At the equipment configuration the table positions are associated to the Modbus registers which are to be made
available. All positions are values of 16 bits. The table size is preset (122 words of 16 bits), the size of the data block
sent to the Profibus network, however, is configurable and may not correspond to the table in its totality.

Status Register

Bit15 Bit14

Bit13 Bit12

Bit11

Bit10 Bit9

Bit8

Bit7

Bit6

Bit5

Bit4

Bit3

Bit2

Bit1

Bit0

DV

WDN

RS1

RS0

ET2

ET1

ET0

EQ

AN7

AN6 AN5

AN4

AN3

AN2

AN1 AN0

Bit 15 – DV (Data Valid) – This bit is inverted, becoming equal to bit 15 of the control register when the input

table has been updated.

Bit 14 – WDN (Write Done) - This bit is inverted, becoming equal to bit 14 of the control register when a

writing operation has been performed in the Modbus network.

Bit 13, Bit 12 – RS1, RS0 (Reset State)

00 – Gateway not reset

01 – At least one reading scan operation of the Modbus already executed

10 – First writing operation performed (invalid)

11 – First reading and first writing operation already performed.

Bit 11, Bit 10, Bit 9 - ET2, ET1, ET0 (Error Type)

000 - No error

001 - Parity error

010 - CRC error

011 – Byte Time out error – response not complete
100 – Response Delay error – no response

101 - Exception error– probable incoherency in the message requested to the slave