NOVUS Controller N2000S User Manual

Page 3

Advertising
background image

Controller N2000S

NOVUS AUTOMATION

3/9

7

7

7

7 – Digital input, Start/Stop control (“RvN

RvN

RvN

RvN”: YES / no).

Closed = outputs enabled
Open = outputs disabled

8

8

8

8 – Invalid selection;
9

9

9

9 – Digital input, holds or allows R&S program progress.

Closed = enables program running;
Opened = holds program (the program resumes normal

operation when the contact is closed again. The
program resumes from the point is was prior to
the hold)

10

10

10

10 – R&S program 1 selection. This option is useful when the user

wants to switch between the main setpoint and a second SP
defined in the ramp and soak program.

Closed = selects program 1;
Open = assumes the main setpoint

11

11

11

11– Configures the I/O5 as an analog 0-20 mA control output.
12

12

12

12– Configures the I/O5 as an analog 4-20 mA control output.
13

13

13

13– Analog 0-20 mA retransmission of PV.
14

14

14

14– Analog 4-20 mA retransmission of PV.
15

15

15

15– Analog 0-20 mA retransmission of SP.
16

16

16

16– Analog 4-20 mA retransmission of SP.

I/O 6 – Digital Input

0

0

0

0 -

Disable the alarm;

6

6

6

6 -

Digital input, manual/automatic selection:

Closed = manual control;
Open = automatic control

7

7

7

7 – Start/Stop control (“RvN

RvN

RvN

RvN”: YES / no).

Closed = outputs enabled
Open = outputs disabled

8

8

8

8 – Invalid selection;
9

9

9

9 - Holds or allows R&S program progress.

Closed = enables program running;
Opened = holds the program (the program resumes normal

operation when the contact is closed again)

10

10

10

10 – R&S program 1 selection. This option is useful when the user

wants to switch between the main setpoint and a second SP
defined in the ramp and soak program.

Closed = selects program 1;
Open = takes the main setpoint

Note: When a function is selected to operate through digital
input, the controller does not respond to the equivalent function
command given in the frontal keypad.

POTENTIOMETER INPUT

The potentiometer of valve position can be seen in the controller. It
must be 10 k

and connections must be as Figure 07 shows. The

potentiometer reading does not power the valve position for control
effects, it only informs the operator the valve current position. The
control action happens regardless of the potentiometer.

In order to visualize the potentiometer reading, the “Pot” parameter
must be enabled. When enabled (YES), the potentiometer position is
displayed on the prompt screen that shows the Manipulated Variable
(MV). When the potentiometer visualization is selected, the MV is not
shown anymore, and the percentage value of valve opening is shown
instead. The MV screen is the second prompt of the main cycle.

ALARM CONFIGURATION

The controller has 2 independent alarms. They can be programmed
to operate with nine different functions, represented in Table 3.

Open sensor

It is activated whenever the input sensor is broken or disconnected.

Event alarm

It activates alarm(s) in specific segments of the program. See item
7.2 in this manual.

Resistance fail

Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.

TYPE

PROMPT

ACTION

Disabled

off

off

off

off

No active alarm. This output can be used as a digital

output to be set by the serial communication.

Sensor

Break

(input Error)

ierr

ierr

ierr

ierr

Alarm will be ON if PV sensor breaks, input signal is

out of range or Pt100 is shorted.

Event
Alarm

(ramp and

Soak)

rs

rs

rs

rs

Can be activated at a specific segment of ramp and

soak program.

Detection

resistance

fail

rfail

rfail

rfail

rfail

Detects a heater broken condition

Low Alarm

lo

lo

lo

lo

SPAn

PV

High Alarm

ki

ki

ki

ki

SPAn

PV

LOW

Differential

difl

difl

difl

difl

SV

PV

SV - SPAn

positive SPAn

SV

PV

SV - SPAn

negative SPAn

HIGH

Differential

difk

difk

difk

difk

SV

PV

SV + SPAn

positive SPAn

SV

PV

SV + SPAn

negative SPAn

Differential

dif

dif

dif

dif

SV

PV

SV + SPAn

SV - SPAn

positive SPAn

SV

PV

SV - SPAn

SV + SPAn

negative SPAn

Table 3 – Alarm functions

SPAn is meant to be the Alarm Setpoints “SPA1”, “SPA2”.

Minimum value

It is activated when the measured value is below the value defined in
the alarm Setpoint.

Maximum value

It is activated when the measured value is above the value defined in
the alarm Setpoint.

Open sensor

It is activated whenever the input sensor is broken or disconnected.

Event alarm

It activates alarm(s) in specific segments of the program. See item
7.2 in this manual.

Resistance fail

Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.

Minimum value

It is activated when the measured value is below the value defined in
the alarm Setpoint.

Maximum value

It is activated when the measured values is above the value defined in
the alarm Setpoint.

Differential (or Band)

In this function, the parameters “SPA1

SPA1

SPA1

SPA1”, “SPA2

SPA2

SPA2

SPA2” represent the PV

deviation as compared to the main SP.

In a positive deviation, the differential alarm will be triggered when
the measured value is out of the range defined in:

( SP – Deviation) and (SP + Deviation)

In a negative deviation, the differential alarm will be triggered when
the measured value is within the range defined above.

Advertising