NOVUS N480I User Manual

Erro

Advertising
background image

5.1

ALARM INITIAL BLOCKING

Alarm blocking at power-up inhibits the relay alarm to trip when the unit is first energized. The alarm will only
trip after the process variable reaches a new alarm situation.

Error alarm shows sensor defects or not properly connected.

6

PROBLEMS WITH THE CONTROLLER

Connection and configuration errors state for most of the problems in using the controller. A final revision of
parameters will save time and further losses.

Error messages are displayed to help the user to identify possible problems.

:

Process temperature is below the selected sensor range.

:

Process temperature is above the selected sensor range

Erro

:

Controller or sensor error. Example: Broken thermocouple or Pt100. Pt100 badly
connected, short-circuited or high cable resistance.

6.2

ELECTRONIC SERIAL NUMBER VISUALIZATION

To read the 8-digit serial number go to the Operation Level and press the

key for 3 seconds. The display

will show the first 4 digits. Then keep the

key pressed for 3 seconds and the display will show the last 4

digits.

FIRST 4 DIGITS

SERIAL NUMBER

LAST 4 DIGITS

When powering the unit the display will show the software version for a few seconds.

7

PRODUCT IDENTIFICATION

The label attached to the controller case identifies the model and the optional present in the product, as
described below:

MODEL: N480I – A – B, where:

A: Outputs:

RP OUT A = Relay and OUT B = Relay

RF OUT A = Relay and OUT B = 24Vdc auxiliary supply

B. Voltage rating:

blank (100-240 Vac/dc) or 24V (24 Vac/dc)

8

TECHNICAL ASSISTANCE

If you encounter a problem with your controller, review the configuration with regard to inputs, outputs,
alarms, etc. If the problem persists, contact your supplier or Novus at [email protected].

MICROPROCESSOR BASED TEMPERATURE

INDICATOR

N 4 8 0 I - V3.1x

OPERATING MANUAL

1

SAFETY SUMMARY

The symbols below are used on the equipment and throughout this document to draw the user’s attention to
important operational and safety information.

CAUTION or WARNING:

Read complete instructions prior to installation

and operation of the unit.

CAUTION or WARNING:

Electrical Shock Hazard

All safety related instructions that appear in the manual must be observed to ensure personal safety and to
prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by
the manufacturer, the protection provided by the equipment may be impaired.

2

SPECIFICATIONS

Dimensions: 48 x 48 x 110 mm (1/16 DIN). Panel cut-out: 45,5 x 45,5 mm. Weight: 150 g (max.);

Power: 100 to 240 Vac / dc (

±

10 %), 50 / 60 Hz or 24 Vdc / ac (

±

10 %); Max. Consumption: 9 VA;

Pt100:

α

=385. 3-wire connection. Excitation current: 0.170 mA;

Accuracy: 0.2 % of full scale for Pt100 and 0,25 % of full scale

±

1 °C for T/C

Thermocouple input impedance: 10 M

A/D converter resolution: 15000 steps

Sampling rate: 10 measurements per second

Environmental conditions: 5 to 50

°

C; Relative humidity (maximum): 80 % up to 30 ºC. For

temperatures above 30 ºC, decrease 3 % per ºC. Installation category II. Pllution degree 2. Altitude <
2000 m.

Front panel: Polycarbonate UL94 V-2; Back panel:ABS + PC UL94 V-0

EMC: EN 61326-1:1997 and EN 61326-1/A1:1998

SAFETY: EN 61010-1: 1993 e EN 61010-1/A2: 1995

INPUT TYPE

CODE

RANGE

Termocouple J

0

0

0

0

-50 to 760 °C (-58 to 1400 °F)

Termocouple K

1

1

1

1

-90 to 1370 °C (-130 to 2498 °F)

Termocouple T

2

2

2

2

-100 to 400 °C (-148 to 752 °F)

Termocouple E

3

3

3

3

-30 to 720 °C (-22 to 1328 °F)

Termocouple N

4

4

4

4

-90 to 1300 °C (-130 to 2372 °F)

Termocouple R

5

5

5

5

0 to 1760 °C (32 to 3200 °F)

Termocouple S

6

6

6

6

0 to 1760 °C (32 to 3200 °F)

Pt100 (Resolution 0.1 °C)

7

7

7

7

-199.9 to 530.0 °C (-199.9 to 986.0 °F)

Pt100 (Resolution 1 °C)

8

8

8

8

-200 to 530 °C (-328 to 986 °F)

4 to 20 mA

9

9

9

9

Linearized J. Maximum range -110 to 760 °C

4 to 20 mA

10

10

10

10

Linearized K. Maximum range -150 to 1370 °C

4 to 20 mA

11

11

11

11

Linearized T. Maximum range -160 to 400 °C

4 to 20 mA

12

12

12

12

Linearized E. Maximum range -90 to 720 °C

4 to 20 mA

13

13

13

13

Linearized N. Maximum range -150 to 1300 °C

4 to 20 mA

14

14

14

14

Linearized R. Maximum range 0 to 1760 °C

4 to 20 mA

15

15

15

15

Linearized S. Maximum range 0 to 1760 °C

4 to 20 mA

16

16

16

16

Linearized Pt100. Max. range -199.9 to 530.0 °C

4 to 20 mA

17

17

17

17

Linearized Pt100. Max. range -200 to 530 °C

0 to 50 mV

18

18

18

18

Linear. Programmable range from -1999 to 9999

4 to 20 mA

19

19

19

19

Linear. Programmable range from -1999 to 9999

0 to 10 V

20

20

20

20

Linear. Programmable range from -1999 to 9999

Table 1 – Types of sensors accepted by the indicator

Advertising