Ѥ warning! ѥ ѥ caution! ѥ, Electrical data, Electrical - line voltage – Comfort-Aire HEH Series 2 to 5 Tons User Manual

Page 22: Hev/h series, Installation, operation & maintenance, Heat controller, llc

Advertising
background image

22

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, LLC.

Electrical Data -

ELECTRICAL - LINE VOLTAGE

WARNING! To avoid possible injury or death
due to electrical shock, open the power
supply disconnect switch and secure it in an
open position during installation.

CAUTION! Use only copper conductors for field
installed electrical wiring. Unit terminals are not
designed to accept other types of conductors.

Electrical - Line Voltage
All field installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for field connections
that must be made by the installing (or electrical)
contractor.

All final electrical connections must be made with a
length of flexible conduit to minimize vibration and sound
transmission to the building.

General Line Voltage Wiring
Be sure the available power is the same voltage and
phase shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the
National Electric Code, whichever is applicable.

ѥ WARNING! ѥ

ѥ CAUTION! ѥ

HE

Model

Volt

Code

Rated Voltage

Voltage

Min/Max

Compressor

HWG

Pump

FLA

Ext

Loop

Pump

FLA

Fan

Motor

FLA

Total

Unit
FLA

Min

Circuit

Amp

Max

Fuse/

HACR

RLA

LRA

Qty

024

1

208-230/60/1

197/252

11.7

58.3

1

0.5

4.0

3.9

20.1

23.0

30

030

1

208-230/60/1

197/252

13.1

73.0

1

0.5

4.0

3.9

21.5

24.7

35

036 1

208-230/60/1

197/252

15.3

83.0

1

0.5

4.0

3.9

23.7

27.5

40

042

1

208-230/60/1

197/252

17.9

96.0

1

0.5

4.0

5.2

27.6

32.0

45

048

1

208-230/60/1

197/252

21.2

104.0

1

0.5

4.0

5.2

30.9

36.2

50

060

1

208-230/60/1

197/252

27.1

152.9

1

0.5

4.0

6.9

38.5

45.2

70

HACR circuit break in U.S. only

Wire length based on one way measurement with 2% voltage drop

All fuses Class RK-5

Wire sizes based on 140°F (60°C) copper conductor