Troubleshooting form, R-410a, Hev/h series – Comfort-Aire HEH Series 2 to 5 Tons User Manual

Page 44

Advertising
background image

44

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, LLC.

TROUBLESHOOTING FORM

COAX

COMPRESSOR

DISCHARGE

SUCTION

HWG

COOLING CYCLE ANALYSIS -

COAX

COMPRESSOR

DISCHARGE

SUCTION

HWG

HEATING CYCLE ANALYSIS -

PSI

SAT

PSI

SAT

°F

°F

AIR

COIL

°F

°F

FP2: HEATING
LIQUID LINE

°F

EXPANSION

VALVE

AIR

COIL

°F

°F

PSI

SAT

PSI

SAT

°F

°F

°F

°F

WATER IN

WATER OUT

PSI

PSI

°F

°F

WATER IN

WATER OUT

PSI

PSI

Heat of Extraction (Absorption) or Heat of Rejection =

________ flow rate (

diff. (

factor = _____________

(Btu/hr)

Superheat

Subcooling

Suction temperature - suction saturation temp.

Discharge saturation temp. - liquid line temp.

=

=

=

=

(deg F)

(deg F)

Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.

Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.

Use 500 for water, 485 for antifreeze.

FLASH

GAS LINE

°F

FP1

SENSOR

°F

EXPANSION

VALVE

FP2: FLASH
GAS LINE

°F

OTHER SIDE
OF FILTR DR

°F

FP1: CLG

LIQ LINE

°F

Refrigerant Type

:

R22

gpm) x ________ temp.

deg. F) x ________ fluid

Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis
using P/T ports to determine water flow and temperature difference. If water-side analysis shows
poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a
last resort.