Unit starting and operating conditions – Comfort-Aire HEH Series 2 to 5 Tons User Manual

Page 33

Advertising
background image

33

Heat Controller, LLC.

HEV/H SERIES

Installation, Operation & Maintenance

Commissioning Limits

Cooling

Heating

Air Limits
Min. ambient air, DB
Rated ambient air, DB
Max. ambient air, DB
Min. entering air, DB/WB
Rated entering air, DB/WB
Max. entering air, DB/WB

45°F [7°C]

80.6° [27°C]

110° [43°C]

50/45°F [10/7°C]

80.6/66.2°F [27/19°C]

110/83°F [43/28°C]

39°F [4°C]
68° [20°C]
85° [29°C]

40°F [4.5°C]

68°F [20°C]
80°F [27°C]

Water Limits
Min. entering water
Normal entering water
Max. entering water

30°F [-1°C]

50-110°F [10-43°C]

120°F [49°C]

20°F [-6.7°C]

30-70°F [-1 to 21°C]

90°F [32°C]

Normal Water Flow

1.5 to 3.0 gpm/ton

[1.6 to 3.2 l/m per KWI

HE Series

Table 9b: Commissioning Limits

Starting/Commissioning Conditions