ELECTRICAL - LO

Figure 21: Low Voltage Field Wiring

Thermostat Connections
The thermostat should be wired directly to the CXM
board. See “Electrical – Thermostat” for specific terminal
connections.

Rev.: 3/24/00

BR

Contactor - CC

Capacitator

Loop PB1 HWG PB2

CXM Control

Low Voltage
Connector

Transformer

CB

Circ Brkr

Grnd

ELECTRICAL - LOW VOLTAGE WIRING

DXM 2

Comp

Relay

24Vdc

EH1
EH2

P6

Off On

JW3

c1

ay

c2

ay

CO

RV

RV

LT1
LT1
LT2
LT2

LP
LP

HP

P7

Status

Fault

CC

CCG

CO

S1

S2

12

1

4

Off On

AO2

P11

Gnd

T1

P10

T2 T2 T3 T3 T4 T4

T5

P9

T5 T6 T6

A0-1 A0-2

Off On

S3

RV

Relay

CCH

Relay

1 2 3 4

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Figure 22: LT1 Limit Setting

DXM2 PCB

JW3-LT1 jumper should be clipped

for low temperature operation

Low Water Temperature Cutout Selection
The DXM2 control allows the fi eld selection of low water (or
water-antifreeze solution) temperature limit by clipping jumper
JW3, which changes the sensing temperature associated
with thermistor LT1. Note that the LT1 thermistor is located on
the refrigerant line between the coaxial heat exchanger and
expansion device (TXV). Therefore, LT1 is sensing refrigerant
temperature, not water temperature, which is a better
indication of how water fl ow rate/temperature is affecting the
refrigeration circuit.

The factory setting for LT1 is for systems using water (30°F
[-1.1°C] refrigerant temperature). In low water temperature
(extended range) applications with antifreeze (most ground
loops), jumper JW3 should be clipped as shown in Figure
19 to change the setting to 10°F [-12.2°C] refrigerant
temperature, a more suitable temperature when using
an antifreeze solution. All residential units include water/
refrigerant circuit insulation to prevent internal condensation,
which is required when operating with entering water
temperatures below 59°F [15°C].