Blower performance data, Hev/h series, Installation, operation & maintenance – Comfort-Aire HEH Series 2 to 5 Tons User Manual

Page 28: Heat controller, llc

Advertising
background image

28

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, LLC.

Table 6: ECM Blower Performance Data Table

Airfl ow in CFM with wet coil and clean air fi lter

Model

Max ESP

(in. wg)

Fan

Motor

(hp)

Range

Cooling Mode

Dehumid Mode

Heating Mode

Fan Only

Mode

Aux/

Emerg

Mode

Stg 2

Stg 1

Stg 2

Stg 1

Stg 2

Stg 1

024

0.75

1/2

Default

750

575

650

500

750

575

350

750

Maximum

850

650

800

600

850

850

850

850

Minimum

600

450

600

450

600

450

300

650

030

0.5

1/2

Default

950

650

800

575

950

650

450

950

Maximum

1100

750

1000

700

1100

1100

1100

1100

Minimum

750

525

750

525

750

525

375

750

036

0.6

1/2

Default

1125

750

975

650

1125

750

525

1125

Maximum

1250

950

1200

800

1250

1250

1250

1250

Minimum

900

600

900

600

900

600

450

900

042

0.6

3/4

Default

1300

925

1125

825

1300

925

600

1300

Maximum

1475

1100

1400

1000

1475

1475

1475

1475

Minimum

1050

750

1050

750

1050

750

525

1050

048

0.75

3/4

Default

1500

1125

1300

975

1500

1125

700

1500

Maximum

1700

1300

1600

1200

1700

1700

1700

1700

Minimum

1200

900

1200

900

1200

900

600

1350

060

0.75

1

Default

1875

1500

1625

1300

1875

1500

875

1875

Maximum

2100

1700

2000

1600

2100

2100

2100

2100

Minimum

1500

1200

1500

1200

1500

1200

750

1500

Airfl ow is controlled within 5% up to the Max ESP shown with wet coil
Factory shipped on default CFM

BLOWER PERFORMANCE DATA