ELECTRICAL - THERMOSTAT WIRING

Figure 24: Typical Thermostat 2 Heat/1 Cool

Thermostat Installation
The thermostat should be located on an interior wall in a
larger room, away from supply duct drafts. DO NOT locate
the thermostat in areas subject to sunlight, drafts or on
external walls. The wire access hole behind the thermostat
may in certain cases need to be sealed to prevent erroneous
temperature measurement. Position the thermostat back
plate against the wall so that it appears level and so the
thermostat wires protrude through the middle of the back
plate. Mark the position of the back plate mounting holes
and drill holes with a 3/16” (5mm) bit. Install supplied
anchors and secure plate to the wall. Thermostat wire must
be 18 AWG wire. Wire the appropriate thermostat as shown
in Figures 24a and 24b to the low voltage terminal strip
on the DXM2 control board. Practically any heat pump
thermostat will work with these units, provided it has the
correct number of heating and cooling stages. However,
using the communicating thermostat (ATC32) is highly
recommended for on-site, easier confi guration, monitoring
and diagnosis.

ATM21U01 Thermostat

Connection to DXM2 Control

Compressor

Heating Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

Y

Y2/W

O
G
R
C

L

Y1

W

O
G
R
C

AL1

DXM2

(Using 2 Heat / 1 Cool thermostat is not

recommended if maximum efficiency is desired)

iGate™ Thermostat

ATC32U**

24Vac Hot

DXM2

24V

Comm +

A+

A+

Comm -

B-

B-

OD

ID

GND

Outdoor

Sensor

(Optiona)

Remote Indoor

Sensor

(Optiona)

24Vac Common

Gnd

R

C

Figure 23a: Communicating Thermostat Connection to
DXM2

Control

Figure 23b: Conventional 3 Heat / 2 Cool Thermostat

Connection to DXM2 Control

CAUTION!

CAUTION! Refrigerant pressure activated water regulating
valves should never be used with manufacturer’s
equipment.

Thermostat

Compressor

Compressor Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

DXM2

Board

Y1
Y2

W

H

O
G
R
C

AL1

Y1
Y2

W

DH

O
G
R

C

L

Dehumidification

Notes:

Auxiliary Heat

1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic

dehumidification

3) DH connection not possible with units with internal pump. Use ATC32U**.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) with
units with internal flow controller.

Communicating Thermostat.

Only use Communicating Thermostat when using Humidifi er (H Input) with
units with internal fl ow controller.