Charging with refrigerant – APC IN ROW RD ACRD101 User Manual

Page 15

Advertising
background image

7

InRow RD 10 kW Air Cooled Operation and Maintenance

Charging With Refrigerant

Calculating R410A charge

Use the following table and formula when calculating the total R410A charge.

Note: All refrigerant pipes must be straight ACR to have 39 bar (565 psig) or above MWP.
Equivalent length of 1/2 in OD discharge line pipe should be kept less than 18 m (60 ft). Total
equivalent length of the discharge line should be less than 46 m (150 ft) to prevent excessive
hot gas pressure drop which can increase the discharge pressure during hot summer days. To
have 61 m (200 ft) total equivalent discharge pipe length the load must be reduced by 5%.

Total charge = Equipment charge + condenser summer charge + condenser flooded charge (for minimum
possible ambient temperature) + liquid R410A in liquid pipe

Equipment charge: 1.6 kg (3.5 lb)

Condenser

model

Selected

ambient

temp. in

°C (°F)

Condenser

summer

charge in

kg (lb)

Condenser flooded charge in kg (lb) for different

minimum outdoor ambient temperatures

4°C (40°F)

-7°C

(20°F)

-18°C (0°F)

-29°C

(-20°F)

-40°C

(-40°F)

ACCD75214

35 (95)

2.2 (4.9)

5.48 (12.1) 5.85 (12.9) 6.03 (13.3)

6.17 (13.6) 6.30 (13.9)

ACCD75214

40 (105)

2.2 (4.9)

5.48 (12.1) 5.85 (12.9) 6.03 (13.3)

6.17 (13.6) 6.30 (13.9)

ACCD75215

46 (115)

3.85 (8.5)

9.57 (21.1) 10.16 (22.4) 10.48 (23.1)

10.70 (23.6) 10.93 (24.1)

ACCD75216

35 (95)

1.36 (3)

3.08 (6.8)

3.26 (7.2)

3.36 (7.4)

3.45 (7.6)

3.49 (7.7)

ACCD75218,

ACCD75220*

40 (105)

1.36 (3)

3.08 (6.8)

3.26 (7.2)

3.36 (7.4)

3.45 (7.6)

3.49 (7.7)

ACCD75217,

ACCD75219

46 (115)

2.27(5)

6.12 (13.5) 6.53 (14.4) 6.71 (14.8)

6.89 (15.2) 7.03 (15.5)

* ACCD75220 is CCC certified for use in China.

Type of fitting or valve - Equivalent length of pipe in m (ft)

ACR pipe size (OD)

Gate valve

Standard elbow 90 ° Reduced coupling

Side outlet T Angle valve

1/2 in

0.18 (0.6)

0.43 (1.4)

0.43 (1.4)

0.82 (2.7)

1.83 (6.0)

5/8 in

0.21 (0.7)

0.49 (1.6)

0.49 (1.6)

0.91 (3.0)

2.13 (7.0)

Recommended Line Sizes

Equivalent length m (ft)

Line Type

Air-cooled ACRD units

15 (50)

Discharge line (horizontal)
Discharge line (vertical)
Liquid line

5/8 inOD ACR
1/2 in OD ACR
1/2 in OD ACR

30 (100

)

Discharge line (horizontal)
Discharge line (vertical)
Liquid line

5/8 inOD ACR
1/2 in OD ACR
1/2 in OD ACR

16 (150)

Discharge line (horizontal)
Discharge line (vertical)
Liquid line

5/8 inOD ACR
1/2 in OD ACR
1/2 in OD ACR