30

High Suction Pres
(High Suction Pressure)

Warning

• Check the air filter and fans for obstructions
• If the problem persists, contact APC at a number on the back cover

of this manual.

Fan Num Fault
(Fan # Fault)

Warning

• A hardware failure exists. For assistance, contact APC at a number

on the back cover of this manual.

Water Detected

Warning

• Identify the source of the leak. Water could be from the condensate

pump, condensate carryover from the evaporator, or condensation.

• For assistance, contact APC at a number on the back cover of this

manual.

Conds Pump Fault
(Condensate Pump Fault)

Warning

• A hardware failure exists. For assistance, contact APC at a number

on the back cover of this manual.

Pan Full
(Condensate Pan Full Fault)

Critical

• Empty the pan and make sure the drain line is not clogged.
• If the problem persists, contact APC at a number on the back cover

of this manual.

Fan PwrSp Fault
(Upper Fan Power Supply
Fault)

Critical

• Make sure the power source is connected properly and the power is

on.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Fan PwrSp Fault
(Lower Fan Power Supply
Fault)

Warning

• Make sure the power source is connected properly and the power is

on.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Air Fltr RnHr Violation
(Air Filter Run Hours
Violation)

Warning

• Reset the Air Filter Run Hours after the air filter is cleaned or

replaced.

Grp Comm Fault
(Group Communication Fault)

Critical

• Make sure the number of cooling units in the group is configured

properly and the A-Link connections between cooling units are
correct.

• Make sure the system is receiving power and is connected properly.
• A hardware failure exists. For assistance, contact APC at a number

on the back cover of this manual.

Sply Air High Temp
(Supply Air High Temperature
Violation)

Warning

• Make sure the Supply Air threshold is set correctly in the Set Unit

Threshlds screen.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Rtn Air High Temp
(Return Air High Temperature
Violation)

Warning

• Make sure the Return Air threshold is set correctly in the Set Unit

Threshlds screen.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Filter DP Sensor Failure

Warning

• Make sure the sensor is connected properly.
• If the problem persists, replace the sensor or contact APC at a

number on the back cover of this manual.

Suction Temperature Sensor
Failure

Warning

• Make sure the sensor is connected properly.
• If the problem persists, replace the sensor or contact APC at a

number on the back cover of this manual.