InRow RD 10 kW Air Cooled Operation and Maintenance

Suction Pressure Sensor Failure

Warning

• Make sure the sensor is connected properly.
• If the problem persists, replace the sensor or contact APC at a

number on the back cover of this manual.

Dischrg Pressure Sensor Failure

Warning

• Make sure the sensor is connected properly.
• If the problem persists, contact APC at a number on the back cover

of this manual.

Input Contact Fault

Warning

• Make sure the Input Normal state is defined correctly in the

Configure Unit> Discrete I/O screen. See page 17 for more
information.

• Clear the problem that caused the input contact switch to change

from the normal state.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Persistent High Discharge
Pressure Fault

Critical

• Indicates there were three High Discharge Pressure shutdowns in

30 minutes. Alarms must be cleared manually.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Persistent Low Suction Pressure
Fault

Critical

• Indicates there were 3 Low Suction Pressure shutdowns in 30

minutes. Alarms must be cleared manually.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Cannot Start Due to Low
Suction Pressure

Critical

• The unit cannot start because the suction (low side) refrigerant

pressure is too low.

• For assistance, contact APC at a number on the back cover of this

manual.

Superheat too Low

Warning

• For assistance, contact APC at a number on the back cover of this

manual.

Rack Inlet
(Rack Inlet Temperature High
Threshold)

Critical

• Make sure the Rack Inlet setting is correct in the Set Unit

Threshlds screen.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Supply Air
(Supply Air Temperature High
Threshold)

Critical

• Make sure the Supply Air setting is correct in the Set Unit

Threshlds screen.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Return Air
(Return Air Temperature
HighThreshold)

Critical

• Make sure the Return Air setting is correct in the Set Unit

Threshlds screen.

• If the problem persists, contact APC at a number on the back cover

of this manual.

Alarm Message

Severity

Action Required