InRow RD 10 kW Air Cooled Operation and Maintenance

8

Quantity of R410A in 1/2 in OD liquid line: (area) x (length in ft) x (density): 0.0010554 (ft

2

) x L (ft) x

61.0 (lbm/ft

3

)

Density of liquid R410A at 40.6

°

C (105

°

F) and 260 psig: 0.98 g/cm

3

(61.0 lbm/ft

3

)

Cross sectional area for 1/2 in OD pipe is 0.0010554 ft

2

.

Liquid line charge for 1/2 in OD ACR copper tube: 0.095 kg/m (0.0644 lb/ft).

Cross sectional area for 5/8 in OD pipe is 0.001619 ft

2

.

Quantity of R410A in 5/8 in OD liquid line: (area) x (length in ft) x (density): 0.001619 (ft

2

) x L (ft) x

61.0 (lbm/ft

3

).

Liquid line charge for 5/8 in OD ACR copper tube: 0.146 kg/m (0.099 lb/ft).

Example:
Calculate the total R410A charge for an FCB5 condenser with 25 ft of 1/2 in OD liquid piping.
Minimum outdoor design temperature is -28.9

°

C (-20

°

F).

Note: Imperial units are used in this example.

Total R410A charge: 3.5 + 4.9 + 13.6 + (25*0.0644) = 23.6 lb.