Troubleshooting – APC IN ROW RD ACRD101 User Manual

Page 52

Advertising
background image

InRow RD 10 kW Air Cooled Operation and Maintenance

44

Troubleshooting

Problem Possible

Cause

Corrective

Action

Controls erratic or
inoperative

• Inlet temperature to cooling

unit is higher than rated
maximum temperature

• Reduce the load or add additional cooling equipment.

Fans fail to start

• Power supplies are not

operating properly

• Confirm that the power supplies are seated properly and fully

engaged. This is indicated by a green LED.

• Confirm that the cooling unit is plugged in and is receiving

power.

• Failed power supply

• Replace the power supply if the LED is red.

• Cooling unit shutd own due to

an external command

• Temporarily remove the user contact cable, if it is connected.

• Single fan fails to start

• Verify that the fan circuit breaker is

O

N

.

Cooling unit cannot
obtain setpoint

• Improper placement of remote

temperature sensor

• Verify that the remote temperature sensor is properly located

in the cold aisle.

• Dirty filter

• Clean the filter.

• Dirty coil

• Clean the coil.

• Application error

• For assistance, contact APC at a number on the back cover of

this manual.

• Heat load is too far away

• Place the cooling unit closer to the heat load.

Water carryover

• Improper fan speed selected

• RACS and HACS modes only. Select the next highest fan

speed setting. For example, change the fan speed setting from
Low to Med/Low.

Temperature control
not tight enough

• Improper placement of remote

temperature sensor

• Verify that the remote temperature sensor is properly located

in the cold aisle.

Water on outside of
cooling unit

• Condensate drain hose is not

connected or not properly
routed outside the cooling unit

• Verify that the condensate drain hose is properly connected to

the pump and properly routed outside of the cooling unit.

• Verify that the condensate drain line does not exceed 4.9

meters (16 feet) lift and 15.4 meters (50.0 feet) horizontal run.

• Leak in piping system

• Locate and repair the leak.

• Cooling unit not leveled

properly

• Adjust the leveling feet of the cooling unit.

• Damaged piping insulation

• Identify damaged area and repair the insulation.

Display interface not
operational but
cooling unit operates

• Display interface not

connected properly

• Verify that the display interface cable is connected properly.

Incorrect air pressure • False filter clogs

• Verify that the ends of the clear plastic air tubes are not

obstructed.

• Verify that the clear plastic air tubes are connected to the

controller.

• Verify that the clear plastic air tubes are not pinched.

Alarms do not show
up on monitoring
equipment (Customer
Output Contact)

• External monitoring equipment

is not receiving power or is not
functioning properly

• Confirm that power, if required, is being supplied to the

external equipment.

• If the cooling unit (+12 V or +24 V) is providing power to the

external equipment, verify that the external equipment is
<50 mA.

• Test the external equipment by bypassing the output contact.
• Verify Customer Output Contact settings. See “Contacts” on

page 17.