COMPLETE TROUBLESHOOTING GUIDE

Day & Night Thermostat

TP1

1 – Before you start

***IMPORTANT: READ AND FOLLOW THESE INSTRUCTIONS BEFORE

STARTING THE TEST.

THE UNIT MUST BE UNPLUGGED

DO NOT PLUG A LOAD INTO THE OUTLET UNTIL STEP 6

LIGHTING CONDITION: Perform this test in a room with enough light
for the controller to detect a DAY condition. A dark location should
be avoided.

TEMPERATURE: Perform this test in a room where ambient
temperature is between 65°F and 85°F (18°C and 30°C).

DEFINITIONS: CW = clockwise, CCW = counterclockwise

TURN BOTH KNOBS FULLY CW BEFORE GOING TO STEP 1

2 – Test

STEP

HANDLING AND TEST DESCRIPTION

EXPECTED RESULTS

1

Plug the unit into the power outlet

WITHIN 5 SECONDS, turn BOTH
KNOBS fully CCW .

Output On indicator
will turn ON

2

Turn UPPER KNOB fully CW.

Output On indicator
will turn OFF.

3

Cover the Light Sensor completely
with the palm of your hand or black
electrical tape(a single finger will
NOT cover the sensor
appropriately)

Output On indicator
will turn ON after 6 to
8 seconds.

7

COMPLETE TROUBLESHOOTING GUIDE

STEP

HANDLING AND TEST DESCRIPTION

EXPECTED RESULTS

4

Keep the Light Sensor fully
covered while turning the
LOWER KNOB fully CW

Output On indicator
will turn OFF again.

5

Uncover the Light Sensor and
wait 6 to 8 sec. THEN rotate the
UPPER KNOB very slowly CCW
until the Output ON indicator
turns ON : leave the knob in this
position.

Output On indicator
will turn ON when the
knob pointer indicates
a temperature close to
the ambient room
temperature. Make
sure this temperature
indication makes
sense.

6

Plug a load (lamp, pump..) into
the TP1 front outlet.

The load will turn ON
(the load ON/OFF
switch, if any, must be
in the ON position).

7

Turn the UPPER KNOB fully CW.

Output On indicator
and the load will turn
OFF.