WWW.SUNLIGHTSUPPLY.COM

Distributed by:

208/230V

System

Breaker

Separate all Power &

Communications Wiring by 2”

Indoor Unit

(Ground)

Outdoor

Unit

F2
F1

G

L1
L2

F2
F1

G

L1
L2

POWER VOLTAGE:

Power Voltage:

208/230V - 1 Ph - 60 Hz

Control Voltage:

DDC Fuzzy Logic

Main Breaker Size:

20 A

CHARGING:

Unit is charged for:

25 ft. (Factory Charge 58.1oz. R410A)

Additional Charge of R410A:

0.16 oz./ft. over 25 ft.

CHARGE FOR LINE RUN LENGTHS:

Length:

25

35

45

55

65

75

85

95

98

Added Charge (oz.):

0

1.6

3.2

4.8

6.4

8.0

9.6 11.2 11.68

INTERCONNECTING WIRING:

Gauge:

14 AWG Power & 16 AWG Shielded Communication

Number of Interconnecting Wires: 3x14 AWG Power & 2x16 AWG Control = 5 Total

LINE SIZES:

“Liquid” (expanded gas) line:

1/4”

Suction:

5/8”

BOTH LINES MUST BE INSULATED SEPARATELY

Samsung MAX 24,000 BTU Mini-Split

Indoor Unit: #700554 (AQN24VFUAGM)

Outdoor Unit: #700556 (AQX24VFUAGM)

INTERCONNECT LENGTH:

Maximum/Minimum Length:

98 feet / 10 feet

Vertical Lift:

50 feet (Trap required at 26 ft.)

Note: Condenser can be above or below evaporator