6. Commissioning, operation

Indication

Unit

dP

Select unit

Confirm

di.Lo

Set the decimal point

Confirm

Set the smallest display

value

Confirm

di.Lo

Setting the largest

display value

Confirm

Set the display

Simultaneously press and hold buttons 1 and 3 for five seconds. The indicator

switches to "UNIT".

Using buttons 2 and 3, select the required unit.

Confirm the unit set, using button 1. The display reverts to "UNIT".

Briefly press button 1 in order to bring up the menu point "dP" (decimal point).

Using buttons 2 and 3, select the required position for the decimal point.

Confirm the position set using button 1. The display reverts to "dP".

Briefly press button 1 in order to bring up the menu point "di.Lo" (display low).

Using buttons 2 and 3, set the display value to be either 4 mA or 0.1 V

Confirm the value set using button 1. The display reverts to "di.Lo".

Briefly press button 1 in order to bring up the menu point "di.Hi" (display high).

Using buttons 2 and 3, set the display value to be either 20 mA or 10.1 V

Confirm the value set using button 1. The display reverts to "di.Hi".

By pressing button 1 briefly, the settings are saved. A successful 'Save' is signalled by

the display switching off briefly.

5 s