Specifications, Specifications models a-as-1, wur-1 – WIKA WUR-1 User Manual

Page 8

Advertising
background image

GB

WIKA operating instructions attachable indicator, models A-AS-1, WUR-1

8

2437704.05 10/2012 GB/D/F/E

Specifications

Models A-AS-1, WUR-1

Indication

Principle

7-segment LED, red, 4-digit, character size 7 mm

Indication range

-999 ... 6000

Accuracy

≤ 0.5 % of span ±1 digit

Housing material

ABS

Scaling adjustment

Menu-driven programming via external control keys

Adjustable measuring range

Freely-selectable decimal point

Programmable pressure units: bar, psi, kg/cm

2

, MPa, kPa

Zero point, freely adjustable in the range ±10 % of span

Input signal

A-AS-1

4 ... 20 mA, 2-wire (power supply from current loop,

6 V voltage drop)

0.1 ... 10.1 V; 3-wire

0.1 ... 5.1 V; 3-wire

WUR-1

4 ... 20 mA; 2-wire (power supply from current loop,

6 V voltage drop)

0 ... 10 V; 3-wire

0 ... 5 V; 3-wire

Output signal

A-AS-1

Analogue current signal is connected through directly

(4 ... 20 mA, 0 ... 10 V or 0 ... 5 V, voltage: offset ≤ 100 mV)

WUR-1

Analogue current signal is connected through directly

(4 ... 20 mA, 0.1 ... 10.1 V or 0.1 ... 5.1 V, voltage: offset ≤ 100 mV)

Max. permissible input

±40 mA (short-term)

±DC 40 V (short-term)

Power supply U

B+

DC 16 ... 30 V for 4 ... 20 mA

DC 15 ... 30 V for 0 ... 10 V

DC 10 ... 30 V for 0 ... 5 V

Influence of supply voltage

< 0.1 % of span/10 V

3. Specifications

3. Specifications