WIKA operating instructions attachable indicator, models A-AS-1, WUR-1

18

2437704.05 10/2012 GB/D/F/E

7. Maintenance and cleaning / 8. Faults

7. Maintenance and cleaning

7.1 Maintenance

This LED attachable indicator is maintenance-free.

Repairs must only be carried out by the manufacturer.

7.2 Cleaning

CAUTION!

Prior to cleaning, disconnect the LED attachable indicator from the

power supply.

Clean the instrument with a moist cloth.

Electrical connections must not come into contact with moisture.

For information on returning the instrument see chapter 9.2 "Return".

8. Faults

If the instrument detects any fault conditions, the corresponding error code will be

displayed.

The following error codes are defined:

Error

Causes

Measures

Err.1

Measuring range

exceeded

Input signal too high

Pressure transmitter defec-

tive/not suitable.

Short-circuit in the connec-

tion cabling of the pressure

transmitter

The error message will reset itself

as soon as the input signal is

once more within the permissible

limits.

Check the pressure transmitter

and the instrument configuration

(e.g. input signal).

Err.2

Measured value below

permissible range

Input signal too low, or

negative

Pressure transmitter defec-

tive/not suitable.

Short-circuit in the connec-

tion cabling of the pressure

transmitter

The error message will reset itself

as soon as the input signal is

once more within the permissible

limits.

Check the pressure transmitter

and instrument configuration