6. Commissioning, operation

By pressing button 1 briefly, the settings are saved. A successful 'Save' is signalled by

the display switching off briefly.

Select unit

Using buttons 2 and 3, select the required unit.

If a unit is skipped during the selection, display in these units is not possible.

Input the Zero Offset (offset)

The zero offset enables an adjustment of the display value shown on the display. Through

the adjustment of the display value, the matching of the unit to specific applications is

possible.

The value input is subtracted from the measured value, i.e. the characteristic curve is

shifted, in parallel, to the zero point.

The zero point offset has no influence on the analogue output signal from

the LED attachable indicator.

Indication

OFFS

Displace the zero point

Confirm

Simultaneously press and hold buttons 1 and 2 for five seconds. The display changes

to "OFFS" (offset).

Using buttons 2 and 3, set the required zero point offset (permissible range ±10 % of

the indication range).

Confirm the zero point offset using button 1. The display reverts to "OFFS".

By briefly pressing button 1, the display value will be shown once more.

The LED attachable indicator for pressure transmitters with voltage outputs are factory

preset with the output signals 0.1 ... 5.1 V or 0.1 ... 10.1 V. To operate the LED attachable

indicator with pressure transmitters with 0 ... 5 V or 0 ... 10 V output signals, an appropri-

ate zero point adjustment should be carried out.