Ai_transducer block parameter list, 8 . .rtd ./ .resistor .specific .parameters, 8 .3 .thermocouple .specific .parameters – WIKA T53 User Manual

Page 20

Advertising
background image

0

AI_TRANSDUCER Block Parameter List

 .8 . .RTD ./ .Resistor .specific .parameters

Parameter

Rel.

Index

FF

Description

Type Store Size

byte

RO /

R/W Min. Max. Default

SENSOR_CONNECTION

35

Connection .to .sensor .1, .select .for .-, .3- .and .4-wire .

connection . .Ignored .if .sensor .1 .is .not .a .resistive .sensor .

Defined .codes:

.

0 .= .  .wires

.

1 .= . 3 .wires

.

 .= . 4 .wires

Un-

signed .

8

SRC

1

R/W

1

COMP_WIRE1

36

Value .in .OHM .to .compensate .line .resistance .when

Sensor .1 .is .a .resistive .sensor, .connected .with . .wires .

Float

SRC

4

R/W

0

100

0

COMP_WIRE2

37

Value .in .OHM .to .compensate .line .resistance .when

Sensor . .is .a .resistive .sensor, .connected .with . .wires .

Float

SRC

4

R/W

0

100

0

SENSOR_CONNECTION_2

38

Connection .to .sensor ., .select .for .-, .3- .and .4-wire .

connection . .Ignored .if .sensor . .is .not .a .resistive .sensor .

Defined .codes:

.

0 .= .  .wires

.

1 .= . 3 .wires

Un-

signed .

8

SRC

1

R/W

0

CABLE_RES1

63

For .3- .or .4-wire .resistance .measurements .

Indicates .the .measured .cable .resistance .in .the .wire .

connected .to .terminal .3 . .For .3-wire .measurements .it .is .

multiplied .by .

Float

D

4

RO

0,0

CABLE_RES2

64

For .4-wire .resistance .measurements .

Indicates .the .measured .cable .resistance .in .the .wire .

connected .to .terminal .6 .

Float

D

4

RO

0,0

RTDX_FACTOR_1

65

Indicates .the .X .factor .for .custom .defined .PtX, .NiX, .CuX .

for .LIN_TYPE

Un-

signed .

16

SRC



R/W

100

RTDX_FACTOR_2

66

Indicates .the .X .factor .for .custom .defined .PtX, .NiX, .CuX .

for .LIN_TYPE_

Un-

signed .

16

SRC



R/W

100

 .8 .3 .Thermocouple .specific .parameters

Parameter

Rel.

Index

FF

Description

Type Store Size

byte

RO /

R/W Min. Max. Default

Rj_TEMP

3

Reference .junction .temperature . .The .unit .of .RJ_TEMP .

is .the .PRIMARY_VALUE_UNIT . .If .PRIMARY_VALUE_

UNIT .is .no .temperature .unit .(e .g . .mV) .RJ_TEMP .is .

stated .in .°C .

Float

D

4

RO

0

Rj_TYPE

33

Select .reference .junction .from .internal .to .fixed .value . .

Ignored .for .sensors .which .are .not .thermocouple .types .

Defined .codes:

. 0 .= .No .reference: . Compensation .is .not .used .(e .g . .for .

. .

TC .type .B) .

. 1 .= .Internal: .

Reference .junction .temperature .is .

. .

measured .by .the .device .itself, .via .

. .

an .internally .mounted .sensor .

.  .= .External: .

The .fixed .value .EXTERNAL_RJ_ .

. .

VALUE .is .used .for .compensation . .

. .

The .reference .junction .must .be .kept . .

. .

at .a .constant .temperature .(e .g . .by .a .

. .

reference .junction .thermostat) .

. 3 .= .Sensor, .-w .: . Reference .junction .temperature .is .

. .

measured .by .external .-wire .con- .

. .

nected .Pt100 .sensor .

. 4 .= .Sensor, .3-w: . Reference .junction .temperature .is . .

. .

measured .by .external .3-wire .con- .

. .

nected .Pt100 .sensor .

Un-

signed .

8

SRC

1

R/W

0

EXTERNAL_Rj_VALUE

34

Fixed .temperature .value .of .an .external .reference .

junction . .The .unit .of .EXTERNAL_RJ_VALUE .is .the .

PRIMARY_VALUE_UNIT . .If .PRIMARY_VALUE_UNIT .is .

no .temperature .unit .(e .g . .mV) .EXTERNAL_RJ_VALUE .is .

stated .in .°C .

Float

SRC

4

R/W -40

(°C)

135

(°C)

0

Rj_COMP_WIRE

4

Value .in .OHM .to .compensate .line .resistance .when

External .RJ .sensor, .connected .with . .wires .is .used .

Float

SRC

4

R/W

0

100

0