4.10 PID Control Block Parameter List

Parameter

Rel.

Index Description

Type Store Size

byte

RO /

R/W Min. Max. Default

ST_REV

1

The .revision .level .of .the .static .data .associated .with .the .

function .block . .To .support .tracking .changes .in .static .para-

meter .attributes, .the .associated .block’s .static .revision .

parameter .will .be .incremented .each .time .a .static .parameter .

attribute .value .is .changed . .Also, .the .associated .block’s .

static .revision .parameter .may .be .incremented .if .a .static .

parameter .attribute .is .written .but .the .value .is .not .changed .

Un-

signed .

16

SRC



RO

0

TAG_DESC



The .user .description .of .the .intended .application .of .the .

block .

Octet .

String

SRC

3

R/W

spaces

STRATEGY

3

The .strategy .field .can .be .used .to .identify .grouping .of .

blocks . .This .data .is .not .checked .or .processed .by .the .block .

Un-

signed .

16

SRC



R/W

0

ALERT_kEY

4

Contains .the .identification .number .of .the .plant .unit . .It .helps .

to .identify .the .location .(plant .unit) .of .an .event .

Un-

signed .

8

SRC

1

R/W

1

55

0

MODE_BLk

5

Contains .the .current .mode .and .the .permitted .and .normal .

mode .of .the .block .

DS-69

Mix

4

Mix

O/S

BLOCk_ERR

6

This .parameter .reflects .the .error .status .associated .with .the .

hardware .or .software .components .associated .with .a .block . .

It .is .a .bit .string, .so .that .multiple .errors .may .be .shown .

Bit .

String

D



RO

PV

7

Either .the .primary .analog .value .for .use .in .executing .the .

function, .or .a .process .value .associated .with .it . . .May .also .be .

calculated .from .the .READBACK .value .of .an .AO .block .

DS-65

D

5

RO

SP

8

The .analog .setpoint .of .this .block .

DS-65

N

5

R/W PV_SCALE .

±10%

OUT

9

The .primary .analog .value .calculated .as .a .result .of .executing .

the .function .

DS-65

N

5

R/W

OUT_SCALE

.

±10%

PV_SCALE

10

The .high .and .low .scale .values, .engineering .units .code, .and .

number .of .digits .to .the .right .of .the .decimal .point .to .be .used .

in .displaying .the .PV .parameter .and .parameters .which .have .

the .same .scaling .as .PV .

DS-68 SRC

11

R/W

0-100%

OUT_SCALE

11

The .high .and .low .scale .values, .engineering .units .code, .and .

number .of .digits .to .the .right .of .the .decimal .point .to .be .used .

in .displaying .the .OUT .parameter .and .parameters .which .

have .the .same .scaling .as .OUT .

DS-68 SRC

11

R/W

0-100%

GRANT_DENY

1

Options .for .controlling .access .of .host .computer .and .local .

control .panels .to .operating, .tuning .and .alarm .parameters .of .

the .block .

DS-70 SRC



R/W

CONTROL_OPTS

13

Options .which .the .user .may .select .to .alter .the .calculations .

done .in .a .control .block .

Bit .

String

SRC



R/W

0

STATUS_OPTS

14

Options .which .the .user .may .select .in .the .block .processing .

of .status .

Bit .

String

SRC



R/W

0

IN

15

The .primary .input .value .of .the .block, .required .for .blocks .

that .filter .the .input .to .get .the .PV .

DS-65

N

5

R/W

PV_FTIME

16

Time .constant .of .a .single .exponential .filter .for .the .PV, .in .

seconds .

Float

SRC

4

R/W

Positive

0

BYPASS

17

The .normal .control .algorithm .may .be .bypassed .through .this .

parameter . .When .bypass .is .set, .the .setpoint .value .(in .per-

cent) .will .be .directly .transferred .to .the .output . .To .prevent .a .

bump .on .transfer .to/from .bypass, .the .setpoint .will .automati-

cally .be .initialized .to .the .output .value .or .process .variable, .

respectively, .and .the .path .broken .flag .will .be .set .for .one .

execution .

Un-

signed .

8

SRC

1

R/W

1



0

CAS_IN

18

This .parameter .is .the .remote .setpoint .value, .which .must .

come .from .another .Fieldbus .block, .or .a .DCS .block .through .

a .defined .link .

DS-65

N

5

R/W

SP_RATE_DN

19

Ramp .rate .at .which .downward .setpoint .changes .are .acted .

on .in .Auto .mode, .in .PV .units .per .second . .If .the .ramp .rate .is .

set .to .zero, .then .the .setpoint .will .be .used .immediately . .For .

control .blocks, .rate .limiting .will .apply .only .in .Auto . .For .out-

put .blocks, .rate .limiting .will .apply .in .Auto, .Cas, .and .RCas .

modes .

Float

SRC

4

R/W

Positive

+INF

SP_RATE_UP

0

Ramp .rate .at .which .upward .setpoint .changes .are .acted .on .

in .Auto .mode, .in .PV .units .per .second . .If .the .ramp .rate .is .set .

to

zero, .then .the .setpoint .will .be .used .immediately . .For .con-

trol .blocks, .rate .limiting .will .apply .only .in .Auto . .For .output .

blocks, .rate .limiting .will .apply .in .Auto, .Cas, .and .RCas .

modes .

Float

SRC

4

R/W

Positive

+INF

SP_hI_LIM

1

The .setpoint .low .limit .is .the .lowest .setpoint .operator .entry .

that .can .be .used .for .the .block .

Float

SRC

4

R/W PV_SCALE .

±10%

100

SP_LO_LIM



The .setpoint .high .limit .is .the .highest .setpoint .operator .entry .

that .can .be .used .for .the .block .

Float

SRC

4

R/W PV_SCALE .

±10%

0