9

Equations: . .
. FIELD_VAL .= .100*(channel .value .- .EU@0%) ./ .(EU@100% .- .EU@0%) .[XD_SCALE] . .
. Direct: .PV .= .channel .value . .
. Indirect: .PV .= .(FIELD_VAL/100) .* .(EU@100% .- .EU@0%) .+ .EU@0% .[OUT_SCALE] . .
. Ind .Sqr .Root: .PV .= .sqrt(FIELD_VAL/100) .* .(EU@100% .- .EU@0%) .+ .EU@0% .[OUT_SCALE] .

3 .5 .Supported .Modes

O/S, .Man .and .Auto .

3 .6 .To .enable .the .Simulation .mode

The .hardware .lock .for .the .simulation .mode .is .a .reed .switch .
mounted .in .the .T53 .transmitter . .The .reed .switch .can .be .activat-
ed .with .a .special .designed .magnet .which .is .mounted .on .the .bus .
connection .terminals .pin .no . .1 .and .pin .no . . . .Magnet .type .no . .
1557596 .can .be .ordered .at .WIKA . .
.
.

3 .7 .Alarm .Types

Standard .block .alarm .plus .standard .HI_HI, .HI, .LO, .and .LO_LO .alarms .applied .to .OUT .

3 .8 .Mode .Handling

Standard .transition .in .and .out .of .O/S . .
Standard .transition .from .Man .to .Auto .and .back . .

3 .9 .Status .Handling

The .status .values .described .in .Output .Parameter .Formal .Model .of .Part .1 .apply, .with .the .ex-
ception .of .the .control .sub-status .values . .The .Uncertain .- .EU .Range .Violation .status .is .always .
set .if .the .OUT .value .exceeds .the .OUT_SCALE .range, .and .no .worse .condition .exists . .The .fol-
lowing .options .from .STATUS_OPTS .apply, .where .Limited .refers .to .the .sensor .limits: .
. Propagate .Fault .Forward .
. Uncertain .if .Limited .
. BAD .if .Limited .
. Uncertain .if .Man .mode

3 .10 .Initialisation

The .PV .filter .must .be .initialised, .but .other .than .that, .no .special .initialisation .is .required . .This .
is .a .pure .calculation .algorithm . .

3.11 Analogue Input Blocks Parameter List, Fieldbus Foundation

Parameter

Rel.

Index Description

Type Store Size

byte

RO /

R/W Min Max Default

ST_REV

1

The .revision .level .of .the .static .data .associated .with .the .func-

tion .block . .To .support .tracking .changes .in .static .parameter .

attributes, .the .associated .block’s .static .revision .parameter .will .

be .incremented .each .time .a .static .parameter .attribute .value .is .

changed . .Also, .the .associated .block’s .static .revision .parameter .

may .be .incremented .if .a .static .parameter .attribute .is .written .

but .the .value .is .not .changed .

Un-

signed .

16

SRC



RO

0

TAG_DESC



The .user .description .of .the .intended .application .of .the .block .

Octet .

String

SRC

3

R/W

Spaces

STRATEGY

3

The .strategy .field .can .be .used .to .identify .grouping .of .blocks . . .

This .data .is .not .checked .or .processed .by .the .block .

Un-

signed .

16

SRC



R/W

0

ALERT_kEY

4

The .identification .number .of .the .plant .unit . .This .information .

may .be .used .in .the .host .for .sorting .alarms, .etc .

Un-

signed .

8

SRC

1

R/W

1

55

0

MODE_BLk

5

The .actual, .target, .permitted, .and .normal .modes .of .the .block .

DS-69

Mix

4

*

1, .1, .5, .

16

BLOCk_ERR

6

This .parameter .reflects .the .error .status .associated .with .the .

hardware .or .software .components .associated .with .a .block . .It .is .

a .bit .string, .so .that .multiple .errors .may .be .shown .

Bit .

String

D



RO

PV

7

Either .the .primary .analog .value .for .use .in .executing .the .func-

tion, .or .a .process .value .associated .with .it . .May .also .be .calcu-

lated .from .the .READBACK .value .of .an .AO .block .

DS-65

D

5

RO