AI_TRANSDUCER Block Parameter List

 .8 .8 .Sensor .calibration, .Description

Sensor .calibration .is .a .very .useful .function .when .the .transmitter .output .needs .to .be .adjusted .to .the .sen-
sor .signal, .e .g . .when .the .temperature .sensor .does .not .correspond .to .the .ideal .values .for .the .selected .
temperature .range . .The .results .depend .on .the .accuracy .of .the .calibrator .or .reference .equipment . .In .the .
following .a .temperature .sensor .calibration .is .described, .however .the .principle .can .be .used .for .all .input .
types .

SENSOR_CAL_METHOD_1 ./ . .defines .the .use .of .either .“Factory .trim .Standard” .(the .factory .defined .val-
ues .calculated .according .to .the .valid .norms) .or .“User .Trim .Standard” .(the .sensor .calibrated .values) .in .
the .transmitter .for .sensor .1 .and . .respectively . .During .sensor .calibration .SENSOR_CAL_METHOD_1 ./ . .
must .be .set .to .“Factory .trim .Standard” .= .103 .

The .sensor .calibration .function .in .T53 .will .change .the .slope .of .the .linarisation .curve .so .the .curve .is .ad-
justed .to .the .connected .sensor . .To .obtain .accurate .temperature .measurement .in .the .range .e .g . .0 . . .100 .
°C .apply .to .the .sensor .a .temperature .e .g . .of .5 .°C .as .the .low .temperature .and .e .g . .95 .°C .as .the .high .tem-
perature .through .a .precise .temperature .calibrator .

At .sensor .calibration .the .succeeding .procedure .must .be .followed .precisely .(Example: .sensor .1):

. 1 . .SENSOR_CAL_METHOD_1 .= .103 .
.  . .Apply .the .low .temperature .of .the .calibrator .to .the .sensor .
. 3 . .CAL_POINT_LO_1 . .= .5 .00 .(type .in .the .low .temperature .of .the .calibrator) .
. 4 . .CAL_ACTUAL_LO_1 .= .1 .00 .(The .measurement .of .the .deviation .starts .by .typing .in .a .random .value) .
. 5 . .Apply .the .high .temperature .of .the .calibrator .to .the .sensor .
. 6 . .CAL_POINT_HI_1 .= .95 .00 .(type .in .the .high .temperature .of .the .calibrator) .
. 7 . .CAL_ACTUAL_HI_1 .= .1 .00 .(The .measurement .of .the .deviation .starts .by .typing .in .a .random .value .
. .

and .T53 .calculates .the .curve .slope .according .to .the .measured . .

. .

deviations .) .

. 8 . .SENSOR_CAL_METHOD_1 .= .104 .(the .sensor .calibration .just .carried .out .is .used)

 .8 .9 .Sensor .Calibration .Parameters

Parameter

Rel.

Index

FF

Description

Type Store Size

byte

RO /

R/W Min. Max. Default

CAL_POINT_LO_1

46

The .low .calibration .value .applied .to .sensor .1 .

The .value .from .either .a .calibrator .or .a .reference .equip-

ment .

Float

SRC

4

R/W

-10

38

CAL_ACTUAL_LO_1

47

Entering .any .value .will .force .the .device .to .automatically .

measure .and .store .the .actual .low .point .value . .Must .be .

entered .with .the .applied .CAL_POINT_LO_1 .value

Float

SRC

4

R/W

-10

38

CAL_POINT_hI_1

48

The .high .calibration .value .applied .to .sensor .1 .

The .value .from .either .a .calibrator .or .a .reference .equip-

ment .

Float

SRC

4

R/W

10

38

CAL_ ACTUAL _hI_1

49

Entering .any .value .will .force .the .device .to .automatically .

measure .and .store .the .actual .high .point .value . .Must .be .

entered .with .the .applied .CAL_POINT_HI_1 .value

Float

SRC

4

R/W

10

38

SENSOR_CAL_METhOD_1

50

Enables .or .disables .the .last .sensor .calibration .for . .

sensor .1 .

103 .= .Factory .trim .standard .(calibration .values .disabled) .

104 .= .User .trim .standard .(calibration .values .enabled)

Un-

signed .

8

SRC

1

R/W

103

SENSOR_CAL_LOC_1

51

The .last .location .of .the .calibrated .sensor

OCTET_

STRING

SRC

3

R/W

” . . . . . .”

SENSOR_CAL_DATE_1

5

The .last .date .on .which .the .calibration .was .performed

7 .* .Un-

signed .

8

SRC

7

R/W

0,0,0,0, .

1,1,103

SENSOR_CAL_WhO_1

53

The .name .of .the .person .responsible .for .the .last .sensor .

calibration

OCTET_

STRING

SRC

3

R/W

” . . . . . .”

CAL_POINT_LO_2

54

The .low .calibration .value .applied .to .sensor . .

The .value .from .either .a .calibrator .or .a .reference .equip-

ment .

Float

SRC

4

R/W

-10

38

CAL_ACTUAL_LO_2

55

Entering .any .value .will .force .the .device .to .automatically .

measure .and .store .the .actual .low .point .value . .Must .be .

entered .with .the .applied .CAL_POINT_LO_ .value

Float

SRC

4

R/W

-10

38