WIKA T53 User Manual

Page 34

Advertising
background image

34

Parameter

Rel.

Index Description

Type Store Size

byte

RO /

R/W Min. Max. Default

GAIN

3

Dimensionless .value .used .by .the .block .algorithm .in .calcu-

lating .the .block .output .

Float

SRC

4

R/W

0

RESET

4

The .integral .time .constant, .in .seconds .per .repeat .

Float

SRC

4

R/W

Positive

+INF

BAL_TIME

5

This .specifies .the .time .for .the .internal .working .value .of .bias .

or .ratio .to .return .to .the .operator .set .bias .or .ratio, .in .sec-

onds . .In .the .PID .block, .it .may .be .used .to .specify .the .time .

constant .at .which .the .integral .term .will .move .to .obtain .bal-

ance .when .the .output .is .limited .and .the .mode .is .Auto, .Cas, .

or .RCas . .

Float

SRC

4

R/W

Positive

0

RATE

6

Defines .the .derivative .time .constant, .in .seconds . .

Float

SRC

4

R/W

Positive

0

BkCAL_IN

7

The .value .and .status .from .a .lower .block’s .BKCAL_OUT .that .

is .used .to .prevent .reset .windup .and .to .initialize .the .control .

loop .

DS-65

N

5

R/W

OUT_hI_LIM

8

Limits .the .maximum .output .value .

Float

SRC

4

R/W

OUT_SCALE

.

±10%

100

OUT_LO_LIM

9

Limits .the .minimum .output .value .

Float

SRC

4

R/W

OUT_SCALE .

±10%

0

BkCAL_hYS

30

The .amount .that .the .output .must .change .away .from .its .out-

put .limit .before .the .limit .status .is .turned .off, .expressed .as .a .

percent .of .the .span .of .the .output .

Float

SRC

4

R/W

0

50

0 .5

BkCAL_OUT

31

The .value .and .status .required .by .an .upper .block’s .BKCAL_

IN .so .that .the .upper .block .may .prevent .reset .windup .and .

provide .bumpless .transfer .to .closed .loop .control .

DS-65

D

5

RO

RCAS_IN

3

Target .setpoint .and .status .provided .by .a .supervisory .Host .

to .a .analog .control .or .output .block .

DS-65

N

5

R/W

ROUT_IN

33

Target .output .and .status .provided .by .a .Host .to .the .control .

block .for .use .as .the .output .(ROut .mode) .

DS-65

N

5

R/W

ShED_OPT

34

Defines .action .to .be .taken .on .remote .control .device .time-

out .

Un-

signed .

8

SRC

1

R/W

0

RCAS_OUT

35

Block .setpoint .and .status .after .ramping .- .provided .to .a .

supervisory .Host .for .back .calculation .and .to .allow .action .to .

be .taken .under .limiting .conditions .or .mode .change .

DS-65

D

5

RO

ROUT_OUT

36

Block .output .and .status .- .provided .to .a .Host .for .back .

calculation .in .ROut .mode .and .to .allow .action .to .be .taken .

under .limited .conditions .or .mode .change .

DS-65

D

5

RO

TRk_SCALE

37

The .high .and .low .scale .values, .engineering .units .code, .and .

number .of .digits .to .the .right .of .the .decimal .point, .associ-

ated .with .TRK_VAL .

DS-68 SRC

11

R/W

0-100%

TRk_IN_D

38

This .discrete .input .is .used .to .initiate .external .tracking .of .the .

block .output .to .the .value .specified .by .TRK_VAL .

DS-66

N



R/W

TRk_VAL

39

This .input .is .used .as .the .track .value .when .external .tracking .

is .enabled .by .TRK_IN_D .

DS-65

N

5

R/W

FF_VAL

40

The .feed .forward .value .and .status .

DS-65

N

5

R/W

FF_SCALE

41

The .feedforward .input .high .and .low .scale .values, .engineer-

ing .units .code, .and .number .of .digits .to .the .right .of .the .deci-

mal .point .

DS-68 SRC

11

R/W

0-100%

FF_GAIN

4

The .gain .that .the .feed .forward .inpt .is .multiplied .by .before .it .

is .added .to .the .calculated .control .output .

Float

SRC

4

R/W

0

UPDATE_EVT

43

This .alert .is .generated .by .any .change .to .the .static .data .

DS-73

D

14

RO

BLOCk_ALM

44

The .block .alarm .is .used .for .all .configuration, .hardware, .con-

nection .failure .or .system .problems .in .the .block . .The .cause .

of .the .alert .is .entered .in .the .subcode .field . .The .first .alert .

to .become .active .will .set .the .Active .status .in .the .Status .

attribute . .As .soon .as .the .Unreported .status .is .cleared .by .

the .alert .reporting .task, .another .block .alert .may .be .reported .

without .clearing .the .Active .status, .if .the .subcode .has .

changed .

DS-7

D

13

R/W

ALARM_SUM

45

The .current .alert .status, .unacknowledged .states, .unreported .

states, .and .disabled .states .of .the .alarms .associated .with .

the .function .block . .

DS-74

Mix

8

R/W

ACk_OPTION

46

Selection .of .whether .alarms .associated .with .the .block .will .

be .automatically .acknowledged . .

0 .= .Auto .Ack .Disabled; .1 .= .Auto .Ack .Enabled .

Bit .

String

SRC



R/W

0

1

0

ALARM_hYS

47

Amount .the .PV .must .return .within .the .alarm .limits .before .

the .alarm .condition .clears . .Alarm .Hysteresis .is .expressed .as .

a .percent .of .the .PV .span .

Float

SRC

4

R/W

0

50

0 .5

hI_hI_PRI

48

Priority .of .the .high .high .alarm .

Un-

signed .

8

SRC

1

R/W

0

15

0

hI_hI_LIM

49

The .setting .for .high .high .alarm .in .engineering .units .

Float

SRC

4

R/W

PV_

SCALE

+INF

+INF

hI_PRI

50

Priority .of .the .high .alarm .

Un-

signed .

8

SRC

1

R/W

0

15

0

Advertising