WIKA CS4R User Manual

Page 11

Advertising
background image

Operating Instructions Temperature Indicating Controller CS4R

V1.2

•

05/2006

- 11 -

5.2 Main setting mode

Character Name,

Description, Setting range

Default value

SV
•

Sets the value for controlled object.

•

Scaling low limit value to scaling high limit value

(For DC voltage and current inputs, the placement of the decimal
point follows the selection)

0°C

5.3 Sub setting mode

Character Name,

Description, Setting range

Default value

AT setting
•

Performs PID auto-tuning. However, when PID auto-tuning does

not finish after 4 hours, PID auto-tuning is shut down compulsory.

•

PID auto-tuning cancellation :

PID auto-tuning performance :

OUT proportional band setting
•

Sets the proportional band.

•

The control action becomes ON/OFF when set to 0.0

•

Setting range: 0.0 … 110.0%

2.5%

Integral time setting
•

Sets the integral time.

•

Setting the value to 0 disables this function.

•

Not available for ON/OFF action.

•

Setting range: 0 … 1000 seconds

200 seconds

Derivative time setting
•

Sets the derivative time.

•

Setting the value to 0 disables this function.

•

Not available for ON/OFF action.

•

Setting range: 0 … 300 seconds

50 seconds

Anti-reset windup setting
•

Sets anti-reset windup.

•

Setting the value to 0 disables this function.

•

Available only for PID action.

•

Setting range: 0 … 100%

50%

OUT proportional cycle setting
•

Sets the proportional cycle value for the control output (OUT).

•

Not available for ON/OFF action or control output analogue

current signal (4 ... 20 mA).

•

Setting range: 1 … 120 seconds

30 seconds
or 3 seconds

Manual reset setting
•

Sets the reset value manually.

•

Available only for P and PD action.

•

± Proportional band converted value

(For DC voltage and current inputs, the placement of the
decimal point follows the selection)

0.0

Alarm setting
•

Sets the action point for the alarm output.

•

Setting the value to 0 or 0.0 disables this function

(excluding Process high and Process low alarms).

When Loop break alarm and Heater burnout alarm are applied
together, the output is common.

•

Not available when “No alarm action” is selected in Alarm

action selection.

•

See (Table 5.3-1). (For DC voltage and DC current inputs, the

placement of the decimal point follows the selection.)

0°C