WIKA CS4R User Manual

Page 9

Advertising
background image

Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 9 -

5. Setup

The sensor input character and temperature unit are indicated on the PV display for approx. 3 seconds after

the power is turned on, and the input range high limit value is indicated on the SV display. (Table 5-1)

(If any other value is set during the Scaling high limit setting, it is indicated on the SV display.)
During this time all outputs and the LED indicators are in OFF status. After that the control starts indicating

actual temperature on the PV display and setting value on the SV display.

(Table 5-1)

Input Scale

range

Resolution

–200 ... 1370 °C

–320 ... 2500 °F

1°C (°F)

K

–199.9 ... 400.0 °C

–199.9 ... 750.0 °F

0.1°C (°F)

J

–200 ...1000 °C

–320 ...1800 °F

1°C (°F)

R

0 ... 1760 °C

0 ... 3200 °F

1°C (°F)

S

0 ... 1760 °C

0 ... 3200 °F

1°C (°F)

B

0 ... 1820 °C

0 ... 3300 °F

1°C (°F)

E

–200 ... 800 °C

–320 ... 1500 °F

1°C (°F)

T

–199.9 ... 400.0 °C

–199.9 ... 750.0 °F

0.1°C (°F)

N

–200 ... 1300 °C

–320 ... 2300 °F

1°C (°F)

PL-

0 ... 1390 °C

0 ... 2500 °F

1°C (°F)

C (W/Re5-26)

0 ... 2315 °C

0 ... 4200 °F

1°C (°F)

–199.9 ... 850.0 °C

–199.9 ... 999.9 °F

0.1°C (°F)

Pt100

–200 ... 850 °C

–300 ... 1500 °F

1°C (°F)

–199.9 ... 500.0 °C

–199.9 ... 900.0 °F

0.1°C (°F)

JPt100

–200 ... 500 °C

–300 ... 900 °F

1°C (°F)

4 ... 20mA DC –1999 ... 9999 *1, *2

1

0 ... 20mA DC –1999 ... 9999 *1, *2

1

0 ... 1V DC

–1999 ... 9999 *1

1

0 ... 5V DC

–1999 ... 9999 *1

1

1 ... 5V DC

–1999 ... 9999 *1

1

0 ... 10V DC

–1999 ... 9999 *1

1


*1: Input range and decimal point place can be changed.
*2: 50

Ω shunt resistor (sold optionally) must be connected between the input terminals.

Advertising