WIKA CS4R User Manual

Page 12

Advertising
background image

Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 12 -

.

and

XX.X are

indicated in
turn.

Heater burnout alarm setting

Sets the heater current value for Heater burnout alarm.

Setting the value to 0.0 disables this function.

Self-holding is not available for the alarm output.

Available only when Heater burnout alarm is added.

Rating:

5A [W10] : 0.0 ... 5.0A
10A [W11] : 0.0 ...10.0A
20A [W12] : 0.0 ... 20.0A
50A [W15] : 0.0 ... 50.0A

0.0A

Loop break alarm action time setting

Sets the action time to assess the Loop break alarm.

Setting the value to 0 disables this function.

Setting range: 0 … 200 minutes

0 minutes

Loop break alarm action span setting

Sets the action span to assess the Loop break alarm.

Setting the value to 0 disables this function.

Thermocouple, RTD inputs:

0 … 150°C (°F) or 0.0 … 150.0°C (°F)

DC voltage and current inputs: 0 … 1500

(The placement of the decimal point follows the selection)

0°C

(Table 5.3-1)

Alarm action type

Setting range

High limit alarm

–(Scaling span) to scaling span

Low limit alarm

–(Scaling span) to scaling span

High/Low limits alarm

0 to scaling span

High/Low limit range alarm

0 to scaling span

Process high alarm

Scaling low limit value to scaling high limit value

Process low alarm

Scaling low limit value to scaling high limit value

High limit alarm with standby

–(Scaling span) to scaling span

Low limit alarm with standby

–(Scaling span) to scaling span

High/Low limits with standby

0 to scaling span

Minimum
negative
setting value:
–199.9 … –1999

Maximum
positive
setting value:
999.9 … 9999

5.4 Auxiliary function setting mode 1

Character Name,

Description, Setting range

Default value

Setting value Lock selection

Locks the setting value to prevent setting errors.

The setting item to be locked is dependent on the designation.

PID auto-tuning cannot be carried out when Lock1 or Lock2

is selected.

(Unlock) : All setting values can be changed.

(Lock 1) : None of setting values can be changed.
(Lock 2) : Only main setting mode can be changed.

Unlock

(Lock 3) : All setting values can be changed except Controller/Converter

function selection. However, do not change each setting item of
Auxiliary function setting mode 2.

Changed data reverts to their former value after power is turned

off because they are not saved in the non-volatile memory. Lock
3 is suitable when our programmable controller (with SVTC) is
used together because it has noting to do with memory life.

Advertising