Operating Instructions Temperature Indicating Controller CS4R

V1.2

•

05/2006

- 13 -

Sensor correction setting
•

Sets the sensor correction value of the sensor.

•

Thermocouple and RTD inputs : –100.0 … 100.0°C (°F)

DC voltage and current inputs : –1000 … 1000

(The placement of the decimal point follows the selection.)

0.0°C

Communication protocol selection
•

Selects communication protocol.

•

Available only when the option Digital interface [5] is added.

•

WIKA protocol

:

Modbus ASCII mode :

Modbus RTU mode

:

WIKA protocol

Instrument number setting
•

Sets an individual instrument number to each CS4R when
connecting plural CS4R in serial communication.

•

Available only when the option Digital interface [5] is added.

•

Setting range: 0 … 95

0

Data transfer rate selection
•

Selects a data transfer rate in accordance with host computer

•

Available only when the option Digital interface [5] is added.

•

2400bps :

4800bps :

9600bps :

19200bps :

9600bps

Parity selection
•

Selects the parity.

•

Not available when the option Digital interface [5] is not added

or when WIKA protocol is selected in Communication protocol
selection

•

None :

Even :

Odd :

Even

Stop bit selection
•

Selects the stop bit.

•

Not available when the option Digital interface [5] is not added

or when WIKA protocol is selected in Communication protocol
selection

•

Setting range: 1 or 2

1