Operating Instructions Temperature Indicating Controller CS4R

V1.2

•

05/2006

- 15 -

OUT high limit setting
•

Sets the OUT high limit value.

•

Not available for ON/OFF action.

•

Setting range: OUT low limit value to 105%

Setting greater than 100% is effective to DC
current output type.

100%

OUT low limit setting
•

Sets the OUT low limit value.

•

Not available for ON/OFF action.

•

Setting range: –5% to OUT high limit value

Setting less than 0% is effective to DC current
output type.

0%

OUT ON/OFF action hysteresis setting
•

Sets the ON/OFF action hysteresis for the OUT.

•

Available only for ON/OFF action (P=0).

•

Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)

DC voltage and current inputs : 1 … 1000

(The placement of the decimal point follows the selection)

1.0°C

Alarm action selection
•

Selects an alarm action type.

No alarm action

:

High limit Alarm

:

Low limit alarm

:

High/Low limits Alarm

:

High/Low limit range Alarm

:

Process high Alarm

:

Process low Alarm

:

High limit alarm with standby

:

Low limit alarm with standby

:

High/Low limits alarm with standby :

No alarm action

Alarm action Energized/Deenergized
•

Selects the alarm action Energized/Deenergized.

•

Not available when “No alarm action” is selected in Alarm action

selection.

•

Energized :

Deenergized :

Energized

Alarm HOLD function selection
•

Selects whether alarm HOLD function is [Used] or not.

If alarm HOLD function is set to [Used], once the alarm
functions, alarm output remains until the power is turned off.

•

Not available when “No alarm action” is selected in Alarm

action selection.

•

Alarm HOLD [Not used] :

Alarm HOLD [Used]

:

Alarm HOLD
[Not used]

Alarm hysteresis setting
•

Sets the alarm hysteresis.

•

Not available when “No alarm action” is selected in Alarm action
selection.

•

Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection.)

1.0°C

Alarm action delayed timer setting
•

Sets the alarm action delayed time. The alarm is activated

when the setting time has passed after the input enters alarm
output range.

•

Not available when “No alarm action” is selected in Alarm action

selection.

0 seconds