Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 8 -

Note

Tighten the terminal screw properly referring to the table below.

Terminal screw

Terminal No.

Torque

M2.6

1 to 4

Max. 0.5 Nm

M2.0

5 to 9

Max. 0.25 Nm

Terminal arrangement







(Fig.

4-1)

MAIN OUTPUT

: Control output

EVENT OUTPUT : Outputs when Alarm, Loop break alarm or Heater burnout alarm (option) is ON.

RS-485

: Serial communication

TC :

Thermocouple

RTD

: Resistance temperature detector

DC

: DC current (DC mA) or DC voltage (DC V)

Shunt resistor

: Shunt resistor 50

Ω for input signal DC current

• Option: Heater burnout Alarm

(1) This alarm is not available for detecting current

under phase control.

(2) Use the current transformer (CT) provided, and pass a

lead wire of the heater circuit into a hole of the CT.

(3)When wiring, keep the CT wire away from any AC source

or load wires to avoid the external interference.

(Fig. 4-2)

Lower part of main body

CT input

Communication
(RS-485)

CT input socket

Power
supply

Heater

CT

POWER SUPPLY

24V AC/DC

POWER SUPPLY

100 to 240V AC MAIN OUTPUT

EVENT

OUTPUT

3A

250V AC
0.1A

24V DC

TC

RTD

DC V

DC mA

50

Ω

(shunt resistor)

No.1

No.6

No.1

No.6

No.1
No.2

No.5
No.6

No.3
No.4

RS-485

COM

COM

NC

YA(-)

YB(+)

NC