5.2 Main setting mode

Character

Name, Function, Setting range

Default value

SV1
Sets set value 1.
Setting range: SV low limit to SV high limit

0 °C

SV2
Sets set value 2.
Available only when the option [SV2] is applied.
Setting range: SV low limit to SV high limit

0 °C


5.3 Sub setting mode

Character

Name, Function, Setting range

Default value

AT setting/Auto-reset setting
Designates auto-tuning Performance or auto-reset Performance.
If the auto-tuning is cancelled during the process, P, I and D

values revert to the former value at which AT is performed.

When auto-tuning has not finished after 4 hours, it is cancelled

automatically.

Auto-reset is cancelled in approximately 4 minutes.

OUT1 proportional band setting
Sets the proportional band for OUT1.
OUT1 becomes ON/OFF action when set to 0 … 0.0
0 … 1000 °C (2000 °F), 0.0 … 999.9 °C (°F) or 0.0 … 100.0 %

10 °C

OUT2 proportional band setting
Sets the proportional band for OUT2.
OUT2 becomes ON/OFF action when OUT1 proportional band is

set to 0 or 0.0.

Not available if option [DT2] is not added or if OUT1 is ON/OFF

action.

0.0 … 10.0 times (multiplying factor to OUT1 proportional band)

1.0 times

Integral time setting
Sets integral time for OUT1.
Setting the value to 0 disables the function.
Not available when OUT1 is ON/OFF action.
Auto-reset can be performed when PD action (I=0).
Setting range: 0 … 1000 seconds

200 seconds

Derivative time setting
Sets derivative time for OUT1.
Setting the value to 0 disables the function.
Not available when OUT1 is ON/OFF action.
Setting range: 0 … 300 seconds

50 seconds

ARW setting
Sets ARW for OUT1.
Available only when PID is the control action.
Setting range: 0 … 100 %

50 %

OUT1 proportional cycle setting
Sets proportional cycle for OUT1.
Not available for control output analogue current signal or when

OUT1 is ON/OFF action.

Setting range: 1 … 120 seconds

30 seconds or
3 seconds