Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 30 -

Attached functions

:

[Setting value lock], [Sensor correction], [Auto/manual control switching],

[Input burnout indication]

Thermocouple and RTD inputs

If the input value exceeds the Indication range high limit value, the PV display blinks “

”, and if

the input value exceeds the Indication range low limit value, the PV display blinks “

”.

If the input value exceeds the Control range, OUT1 and OUT2 are turned off (for Control output analogue
current signal: OUT1 low limit value and OUT2 low limit value).
(However, for manual control, it outputs the preset manipulated variable)

Input

Input range

Indication range

Control range

–199.9 ... 400.0 °C

–199.9 ... 450.0 °C

–205.0 ... 450.0 °C

K,T

–199.9 ... 750.0 °F

–199.9 ... 850.0 °F

–209.0 ... 850.0 °F

–200 ... 1370 °C

–250 ... 1420 °C

–250 ... 1420 °C

K

–320 ... 2500 °F

–370 ... 2550 °F

–370 ... 2550 °F

–200 ... 1000 °C

–250 ... 1050 °C

–250 ... 1050 °C

J

–320 ... 1800 °F

–370 ... 1850 °F

–370 ... 1850 °F

0 ... 1760 °C

–50 ... 1810 °C

–50 ... 1810 °C

R,S

0 ... 3200 °F

–50 ... 3250 °F

–50 ... 3250 °F

0 ... 1820 °C

–50 ... 1870 °C

–50 ... 1870 °C

B

0 ... 3300 °F

–50 ... 3350 °F

–50 ... 3350 °F

–200 ... 800 °C

–250 ... 850 °C

–250 ... 850 °C

E

–320 ... 1500 °F

–370 ... 1550 °F

–370 ... 1550 °F

–200 ... 1300 °C

–250 ... 1350 °C

–250 ... 1350 °C

N

–320 ... 2300 °F

–370 ... 2350 °F

–370 ... 2350 °F

0 ... 1390 °C

–50 ... 1440 °C

–50 ... 1440 °C

PL-

0 ... 2500 °F

–50 ... 2550 °F

–50 ... 2550 °F

0 ... 2315 °C

–50 ... 2365 °C

–50 ... 2365 °C

C(W/Re5-26)

0 ... 4200 °F

–50 ... 4250 °F

–50 ... 4250 °F

–199.9 ... 850.0 °C

–199.9 ... 900.0 °C

–210.0 ... 900.0 °C

–200 ... 850 °C

–210 ... 900 °C

–210 ... 900 °C

–199.9 ... 999.9 °F

–199.9 ... 999.9 °F

–211.0 ... 1099.9 °F

Pt100

–300 ... 1500 °F

–318 ... 1600 °F

–318 ... 1600 °F

–199.9 ... 500.0 °C

–199.9 ... 550.0 °C

–206.0 ... 550.0 °C

–200 ... 500 °C

–206 ... 550 °C

–206 ... 550 °C

–199.9 ... 900.0 °F

–199.9 ... 999.9 °F

–211.0 ... 999.9 °F

JPt100

–300 ... 900 °F

–312 ... 1000 °F

–312 ... 1000 °F

DC current and voltage inputs
(4 … 20 mA DC, 0 … 20 mA DC, 0 … 1 V DC, 0 … 5 V DC, 1 … 5 V DC, 0 … 10 V DC)

If input value exceeds Indication range high limit value, PV display blinks “

”, and if input value

exceeds the Indication low limit range, the PV display blinks “

”.

If input value exceeds the Control range, OUT1 and OUT2 are turned ON or OFF, depending on which
has been selected in the [Output status selection when input burnout] (for Control output analogue
current signal: OUT1 high or low limit value, OUT2 high or low limit value).
However, for manual control, it outputs the preset manipulated variable.
Indication range

: [Scaling low limit value – Scaling span x 1 %]

to [Scaling high limit value +Scaling span x 10 %]

(If the input value exceeds the range –1999 … 9999, the PV display blinks

” or “

”)

Control range

: [Scaling low limit value – Scaling span x 1 %]

to [Scaling high limit value +Scaling span x 10 %]

DC input burnout

: When DC input is burnt out, PV display blinks “

” for 4 … 20 mA DC

and 1 … 5 V DC inputs, and “

” for 0 … 1 V DC input.

For 0 … 20 mA DC, 0 … 5 V DC and 0 … 10 V DC inputs, the PV display

indicates the corresponding value with which 0 mA or 0 V is inputted.