Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 28 -

9. Specifications


9.1 Standard specifications


Mounting method

: Flush

Setting

method

: Input system using membrane sheet key

Display

PV display

: Red LED 4 digits, character size 10.2 x 4.9 mm (H x W)

SV display

: Green LED 4 digits, character size 8.8 x 4.9 mm (H x W)

Accuracy (Setting and Indication)

:

Thermocouple

:

Within

±0.2 % of each input span ±1digit, or within ±2 °C (4 °F),

whichever

is

greater

However R, S inputs 0 … 200 °C (400 °F): Within ±6 °C (12 °F)

B input, 0 … 300 °C (600 °F): Accuracy is not guaranteed

K, J, E, T, N inputs less than 0 °C (32 °F): Within ±0.4 % of input span±1digit

RTD

: Within ±0.1 % of each input span ±1 digit, or

within ±1 °C (2 °F), whichever is greater

DC current

: Within ±0.2 % of each input span ±1 digit

DC voltage

: Within ±0.2 % of each input span ±1 digit

Input sampling period

: 0.25 seconds

Input

Thermocouple : K, J, R, S, B, E, T, N, PL- , C(W/Re5-26)

External resistance

: 100

Ω or less

(However, B input: External resistance: 40

Ω or less)

RTD

: Pt100, JPt100, 3-wire system

Allowable input lead wire resistance : 10

Ω or less per wire

DC current

: 0 … 20mA DC, 4 … 20mA DC

Input impedance

: External shunt resistor 50

Ω

Allowable input current

: 50mA or less

DC voltage

: 0 … 1V DC

Input impedance

: 1 M

Ω or greater

Allowable input voltage

: 5 V or less

Allowable signal source resistance : 2 k

Ω or less

: 0 … 5V DC, 1 … 5V DC, 0 … 10V DC

Input impedance

: 100 k

Ω or greater

Allowable input voltage

: 15 V or less

Allowable signal source resistance : 100

Ω or less

OUT1 output

Relay contact : 1a, Control capacity 3 A 250 V AC (resistive load)

1 A 250 V AC (inductive load cosø = 0.4)

Electrical life 100,000 times

Logic level DC 0/12 V (non contact voltage for SSR drive):

12

+ 2

- 0

V DC maximum 40 mA (short circuit protected)

analogue current signal:

4 … 20 mA DC, Load resistance maximum 550

Ω

A1 output

Action

: ON/OFF action

Hysteresis

: 0.1 … 100.0 °C (°F), or 1 … 1000

Output

:

Relay

contact

1a

Control capacity 3 A 250 V AC (resistive load)

Electrical life 100,000 times