WIKA CS4S User Manual

Page 15

Advertising
background image

Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 15 -

OUT2 proportional cycle setting
Sets proportional cycle for OUT2.
Not available if the option [DT2] is not applied or when OUT2 is

ON/OFF action.

Setting range: 1 … 120 seconds

3 seconds

A1 setting
Sets action point for A1 output.
Not available if No alarm action is selected in A1 action selection
Refer to (Table 5.3-1).

0 °C

A2 setting
Sets action point for A2 output.
Not available if option [2AS] or [2AL] is not applied or if No Alarm

action is selected in A2 action selection.

Refer to (Table 5.3-1).

0 °C

. ,

XX.X

indicated
in turn

Heater burnout alarm setting
Sets the heater current value for Heater burnout alarm.
Self-holding is not available for the alarm output.
Available only when the option [W1x] is added.
Rating 5A : 0.0 … 5.0 A

Rating 10A : 0.0 … 10.0 A

Rating 20A : 0.0 … 20.0 A

Rating 50A : 0.0 … 50.0 A

0.0 A

Loop break alarm action time setting
Sets the time to assess the Loop break alarm.
Available only when the option [2AR] or [2AL] is applied.
Setting range: 0 … 200 minutes

0 minutes

Loop break alarm action span setting
Sets the temperature to assess the Loop break alarm.
Available only when the option [2AR] or [2AL] is applied.
Setting range: 0 … 150 °C (°F), 0.0 … 150.0 °C (°F) or

0 … 1500

0 °C

(Table

5.3-1)

Alarm action type

Setting range

High limit alarm

– (Input span) to input span °C (°F)

*1

Low limit alarm

– (Input span) to input span °C (°F)

*1

High/Low limits alarm

0 to input span °C (°F)

*1

High/Low limit range alarm

0 to input span °C (°F)

*1

Process high alarm

Input range low limit value to input range high limit value *2

Process low alarm

Input range low limit value to input range high limit value *2

High limit alarm with standby

– (Input span) to input span °C (°F)

*1

Low limit alarm with standby

– (Input span) to input span °C (°F)

*1

High/Low limits alarm with standby

0 to input span °C (°F)

*1


When input has a decimal point, the negative low limit value is –199.9, and the positive high limit
value is 999.9.

All alarm actions except process alarms are ±deviation setting to the main setting.
*1: For DC input, the input span is the same as the scaling span.
*2: For DC input, input range low (high) limit value is the same as scaling low (high) limit value.