Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 17 -

5.5 Auxiliary function setting mode 2

Character Name, Function, Setting range

Default value

Input type selection
• The input type can be selected from thermocouple (10 types),

RTD (2 types), DC current (2 types) and DC voltage (4 types),
and the unit °C/°F can be selected as well.

• When changing the input from DC voltage to other inputs,

remove the sensor connected to this controller first, then change
for the input. If the input is changed with the sensor connected,
the input circuit may be broken.

K
(

–200 … 1370 °C)

K

–200 ... 1370°C:

–199.9 ... 400.0°C:

J

–200 ... 1000°C:

R

0 ... 1760°C:

S

0 ... 1760°C:

B

0 ... 1820°C:

E

–200 ... 800°C:

T

–199.9 ... 400.0°C:

N

–200 ... 1300°C:

PL-

0 ... 1390°C:

C (W/Re5-26)

0 ... 2315°C:

Pt100

–199.9 ... 850.0°C:

JPt100

–199.9 ... 500.0°C:

Pt100

–200 ... 850°C:

JPt100

–200 ... 500°C:

4 ... 20mA

–1999 ... 9999:

0 ... 20mA

–1999 ... 9999:

0 ... 1V

–1999 ... 9999:

0 ... 5V

–1999 ... 9999:

1 ... 5V

–1999 ... 9999:

0 ... 10V

–1999 ... 9999:

K

–320 ... 2500°F:

–199.9 ... 750.0°F:

J

–320 ... 1800°F:

R

0 ... 3200°F:

S

0 ... 3200°F:

B

0 ... 3300°F:

E

–320 ... 1500°F:

T

–199.9 ... 750.0°F:

N

–320 ... 2300°F:

PL-

0 ... 2500°F:

C (W/Re5-26) 0 ... 4200°F:

Pt100

–199.9 ... 999.9°F:

JPt100

–199.9 ... 900.0°F:

Pt100

–300 ... 1500°F:

JPt100

–300 ... 900°F:

Scaling high limit setting
• Sets scaling high limit value.
• Available only for DC inputs
• Setting range: Scaling low limit value to input range high limit value

9999

Scaling low limit setting
• Sets scaling low limit value.
• Available only for DC inputs
• Setting range: Input range low limit value to scaling high limit value

–1999

Decimal point place selection
• Selects decimal point place.
• Available only for DC inputs
• No decimal point:

1 digit after decimal point:

2 digits after decimal point:

3 digits after decimal point:

No decimal
point

PV filter time constant setting
• Sets process value filter time constant. (If the value is set too

large, it affects control result due to the delay of response)

• Setting range: 0.0 … 10.0 seconds

0.0 seconds

OUT1 high limit setting
• Sets the high limit value of OUT1.
• Not available when OUT1 is ON/OFF action
• Setting range: OUT1 low limit value to 105 %

(Setting greater than 100 % is only effective to Control output

analogue current signal)

100 %