• Main collector duct should be sized according to

specifications shown below.

NOTE: Main collector duct should be equipped with
an auxiliary fan that can maintain the duct airflow at
a minimum of 1200 feet (366 m) per minute. If you do
not have a fan, clean the main collector duct at least
twice a year.

D039IE3A

WEATHER HOOD

OR SWEEP ELBOW

(No cap or screen)

WALL

PARAPET

ROOF

180˚ SWEEP

ELBOW
(No cap

or screen)

24" MIN.

(60.96 cm)

MAIN COLLECTOR DUCT

MAIN COLLECTOR DUCT

Number

of Dryers

Minimum Diameter of

Horizontal Collector Duct

Minimum Diameter of

Vertical Collector Duct

2

7 inch (17.8 cm)

8 inch (20.3 cm)

3

8 inch (20.3 cm)

9 inch (22.9 cm)

4

9 inch (22.9 cm)

10 inch (25.4 cm)

5

10 inch (25.4 cm)

11 inch (27.9 cm)

6

11 inch (27.9 cm)

12 inch (30.5 cm)

7

12 inch (30.5 cm)

13 inch (32.6 cm)

8

12 inch (30.5 cm)

14 inch (35.6 cm)

9

13 inch (32.6 cm)

15 inch (38.1 cm)

10

14 inch (35.6 cm)

15 inch (38.1 cm)

11

14 inch (35.6 cm)

16 inch (40.6 cm)