Step 6 - adjust factory-installed options, Step 6 —adjust factory-installed options – Bryant 551C User Manual

Page 22

Advertising
background image

22

Step 6

—Adjust Factory-Installed Options

Perfect HumidityAdaptive Dehumidification

System
Perfect Humidity system operation can be controlled by field

installation of a Bryant--approved humidistat. (See Fig. 13.)
NOTE: A light commercial Thermidistat™ device (Fig. 14) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided.

% RELATIVE HUMIDITY

C06358

Fig. 13

--- Accessory Field--Installed Humidistat

C06359

Fig. 14

--- Light Commercial Thermidistat Device

To install the humidistat:

1. Route humidistat cable through hole provided in unit

control box.

2. Some models may be equipped with a raceway built into

the corner post on the left side of control box (See Fig.
12.) This raceway provides the required clearance between
high--voltage and low voltage wiring. For models without

a raceway, ensure to provide the NEC required clearance
between high--voltage and low--voltage wiring.

3. Use a wire nut to connect humidistat cable into low-

voltage wiring as shown in Fig. 15.

To install Thermidistat device:

1. Route Thermidistat cable through hole provided in unit

control box.

2. Some models may be equipped with a raceway built into

the corner post on the left side of control box (See Fig.
12.) This raceway provides the required clearance between
high--voltage and low voltage wiring. For models without

a raceway, ensure to provide the NEC required clearance
between high--voltage and low--voltage wiring.

3. A field-supplied relay must be installed between the

thermidistat

and

the

Perfect

Humidity

circuit

(recommended relay: HN61KK324). (See Fig. 16.) The

relay coil is connected between the DEHUM output and C
(common) of the unit. The relay controls the Perfect

Humidity solenoid valve and must be wired between the
Perfect Humidity fuse and the low-pressure switch. Refer
to the installation instructions included with the Bryant

Light Commercial Thermidistat device for more
information.

Disconnect Switch
The optional disconnect switch is non--fused. The switch has the

capability of being locked in place for safety purposes.
Manual Outdoor Damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:

1. Determine quantity of ventilation required for building.

Record amount for use in Step 8.

2. Remove and save outdoor air opening panel and screws.

(See Fig. 17.)

3. Remove evaporator coil access panel. Separate hood and

screen from basepan by removing the 4 screws securing

them. Save all screws.

4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See

Fig. 18 for hood details. Secure top of hood with the
4 screws removed in Step 3. (See Fig. 19.)

6. Remove and save 6 screws (3 on each side) from sides of

the manual outdoor-air damper.

7. Align screw holes on hood with screw holes on side of

manual outdoor-air damper. (See Fig. 18 and 19.) Secure
hood with 6 screws from Step 6.

8. Adjust minimum position setting of the damper blade by

adjusting the manual outdoor-air adjustment screws on the

front of the damper blade. (See Fig. 17.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 20. Tighten screws.

9. Remove and save screws currently on sides of hood.

Insert screen. Secure screen to hood using the screws. (See

Fig. 19.)

Convenience Outlet
An optional convenience outlet provides power for rooftop use.

For maintenance personnel safety, the convenience outlet power

is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.