Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humidity

load on any zone is the fresh air introduced. For some
applications, a device such as an energy recovery unit can be

added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most

cases, the normal heating and cooling processes are more than

adequate to remove the humidity loads for most commercial
applications.
If normal rooftop heating and cooling operation is not adequate
for the outdoor humidity level, an energy recovery unit and/or a

dehumidification option should be considered.

Step 7

—Adjust Evaporator--Fan Speed

Adjust evaporator-fan speed to meet jobsite conditions.
Tables 8 and 9 show fan rpm at motor pulley settings for the

551C 024--060 and 551B 036--072 units. Tables 10 and 13 show
maximum amp draw of belt-drive motor. Table 12 shows sound

data. Refer to Tables 14-33 for performance data. See Table 34

for accessory static pressure drop. See Fig. 39 for the Perfect
Humidity™ system static pressure drops.
For units with electric heating, required minimum cfm is 900 for
551B/C 036; 1200 for 551B/C 048; 1500 for 551B/C 060 and

1800 for 551B 072 and 600 for 551C 024.
Belt Drive Motors
Fan motor pulleys are factory set for speed shown in Table 1.
Check pulley alignment and belt tension prior to start-up.
To change fan speed:

1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts.

(See Fig. 40.)

3. Loosen movable pulley flange setscrew (See Fig. 41).

4. Screw movable flange toward fixed flange to increase

speed and away from fixed flange to decrease speed.

Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 1.

5. Set movable flange at nearest keyway of pulley hub and

tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)

6. Adjust belt tension and align fan and motor pulleys per

guidance below.

NOTE: Once the required flange position is determined for the
correct blower rpm, it is recommended (but not required) that the
variable pitch pulley be replaced with a corresponding size fixed
sheave pulley.
To align fan and motor pulleys:

1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mount-

ing.

To adjust belt tension:

1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for

proper belt tension (

1

/

2

-in. deflection with 7 to 10 lb of

force).

3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed

position.

Table 7—CO

2

Sensor Standard Settings

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Proportional

Any

0-10V

4-20 mA

0-2000

1000

50

2

Interface w/Standard

Building Control System

Proportional

Any

2-10V

7-20 mA

0-2000

1000

50

3

Building Control System

Exponential

Any

0-10V

4-20 mA

0-2000

1100

50

4

Proportional

15

0-10V

4-20 mA

0-1100

1100

50

5

E

i

Proportional

20

0-10V

4-20 mA

0- 900

900

50

6

Economizer

Exponential

15

0-10V

4-20 mA

0-1100

1100

50

7

Exponential

20

0-10V

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

0-10V

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/

Loading Docks

Proportional

0-10V

4-20 mA

0-2000

700

50

LEGEND

ppm — Parts Per Million

551B