Troubleshooting, Unit troubleshooting, Economi$er iv troubleshooting – Bryant 551C User Manual

Page 57

Advertising
background image

57

TROUBLESHOOTING

Unit Troubleshooting

Refer to Tables 35-37 for unit troubleshooting details.

Economi$er IV Troubleshooting

See Table 38 for EconoMi$er IV logic.
A functional view of the EconoMi$er IV is shown in Fig. 61.
Typical settings, sensor ranges, and jumper positions are also

shown. An EconoMi$er IV simulator program is available from

your Bryant distributor to help with EconoMi$er IV training and
troubleshooting.
EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for

troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied with
the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.

1. Disconnect power at TR and TR1. All LEDs should be

off. Exhaust fan contacts should be open.

2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor

across T and T1.

5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S

O

and +.

Connect 1.2 kilo-ohm 4074EJM checkout resistor across

terminals S

O

and +.

8. Put 620-ohm resistor across terminals S

R

and +.

9. Set minimum position, DCV set point, and exhaust

potentiometers fully CCW (counterclockwise).

10. Set DCV maximum position potentiometer fully CW

(clockwise).

11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.

Differential Enthalpy
To check differential enthalpy:

1. Make sure EconoMi$er IV preparation procedure has been

performed.

2. Place 620-ohm resistor across S

O

and +.

3. Place 1.2 kilo-ohm resistor across S

R

and +. The Free

Cool LED should be lit.

4. Remove 620-ohm resistor across S

O

and +. The Free Cool

LED should turn off.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

Single Enthalpy
To check single enthalpy:

1. Make sure EconoMi$er IV preparation procedure has been

performed.

2. Set the enthalpy potentiometer to A (fully CCW). The

Free Cool LED should be lit.

3. Set the enthalpy potentiometer to D (fully CW). The Free

Cool LED should turn off.

4. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:

1. Make sure EconoMi$er IV preparation procedure has been

performed.

2. Ensure terminals AQ and AQ1 are open. The LED for

both DCV and Exhaust should be off. The actuator should
be fully closed.

3. Connect a 9-v battery to AQ (positive node) and AQ1

(negative node). The LED for both DCV and Exhaust

should turn on. The actuator should drive to between 90
and 95% open.

4. Turn the Exhaust potentiometer CW until the Exhaust

LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should

remain in position.

5. Turn the DCV set point potentiometer CW until the DCV

LED turns off. The DCV LED should turn off when the

potentiometer is approximately 9 v. The actuator should
drive fully closed.

6. Turn the DCV and Exhaust potentiometers CCW until the

Exhaust LED turns on. The exhaust contacts will close 30
to 120 seconds after the Exhaust LED turns on.

7. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:

1. Make sure EconoMi$er IV preparation procedure has been

performed.

2. Connect a 9-v battery to AQ (positive node) and AQ1

(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.

3. Turn the DCV Maximum Position potentiometer to

midpoint. The actuator should drive to between 20 and

80% open.

4. Turn the DCV Maximum Position potentiometer to fully

CCW. The actuator should drive fully closed.

5. Turn the Minimum Position potentiometer to midpoint.

The actuator should drive to between 20 and 80% open.

6. Turn the Minimum Position Potentiometer fully CW. The

actuator should drive fully open.

7. Remove the jumper from TR and N. The actuator should

drive fully closed.

8. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

Supply--Air Input
To check supply-air input:

1. Make sure EconoMi$er IV preparation procedure has been

performed.

2. Set the Enthalpy potentiometer to A. The Free Cool LED

turns on. The actuator should drive to between 20 and

80% open.

3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The

actuator should drive fully open.

4. Remove the jumper across T and T1. The actuator should

drive fully closed.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.