PRE-START-UP

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
1. Follow recognized safety practices and wear

protective goggles when checking or servicing a

refrigerant system.

2. Do not operate the compressor or provide any electric

power to the unit unless the compressor terminal

cover is in place and secured.

3. Do not remove the compressor terminal cover until

all electrical sources are disconnected and

tagged withlockout tags.

4. Relieve all pressure from the system before touching

or disturbing anything inside the terminal box if a

refrigerant leak is suspected around the compressor

terminals. Use accepted methods to recover the

refrigerant.

5. Never attempt to repair a soldered connection while

the refrigerant system is under pressure.

6. Do not use a torch to remove any component. The

system contains oil and refrigerant under pressure. To

remove a component, wear protective goggles and

proceed as follows:

a. Shut off electrical power to the unit and tag

disconnect.

b. Recover refrigerant to relieve all pressure

from the system using both high-pressure

and low-pressure ports.

c. Cut component connection tubing with a

tubing cutter, and remove the component

from the unit.

d.Carefully unsweat the remaining tubing

stubs when necessary. Oil can ignite when

exposed to a torch flame.

!

WARNING

Proceed as follows to inspect and prepare the unit for initial

start-up:

1. Remove all access panels.
2. Read and follow instructions on all WARNING,

CAUTION, and INFORMATION labels attached to, or

shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as

broken lines, loose parts, or disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and on

unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using

electronic leak detector, halide torch, or liquid-soap
solution.

c. Inspect all field-wiring and factory-wiring connections.

Be sure that connections are completed and tight. Be sure
that wires are not in contact with refrigerant tubing or

sharp edges.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that condenser-fan blade are correctly

positioned in fan orifice. See Condenser-Fan Adjustment
section for more details.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain trap is filled with water

to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts

have been removed.

START-UP

Unit Preparation

Make sure that the unit has been installed in accordance with

installation instructions and applicable codes.

Return--Air Filters

Make sure the correct filters are installed in the unit (See Table 1).
Do not operate the unit without return-air filters.

Outdoor--Air Inlet Screens

Outdoor-air inlet screen(s) must be in place before operating the
unit.

Compressor Mounting

Compressors are internally spring mounted. Do not loosen or

remove the compressor holddown bolts.

Internal Wiring

Check all electrical connections in unit control boxes; tighten

them as required.

Refrigerant Service Ports

Each unit system has 4 Schrader--type service ports: one on the

suction line, one on the liquid line, and 2 on the compressor

discharge line. Be sure that caps on the ports are tight.

High Flow Valves

Two high flow refrigerant valves are located on the hot gas tube

coming out of the compressor and the suction tubes. Large black
plastic caps distinguish these valves with O--rings located inside

the caps. No field access to these valves is available at this time.

Ensure the plastic caps are in place and tight or the possibility of
refrigerant leakage could occur.

Compressor Rotation

On 3-phase units be certain that the compressor is rotating in the
proper direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect the service gauges to suction and discharge

pressure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:

1. Note that the indoor fan (060 and 072 three-phase units

only) is probably also rotating in the wrong direction.

2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.

The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes more noise and does not provide cooling.

551B

,C