Performance data – Bryant 551C User Manual

Page 34

Advertising
background image

34

Table 14 — Evaporator-Fan Motor Efficiency

MOTOR 551B

EFFICIENCY

024, 036, 048

75

060

74/84*

072

84

*Single-phase/3-phase.

NOTE: Convert watts to bhp using the following formula:

watts input x motor efficiency

bhp =

746

GENERAL FAN PERFORMANCE NOTES

1. Values include losses for filters, unit casing, and wet coils. See Table 12 and 13 and Fig. 36 for accessory/FIOP static pressure

information.

2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the

fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

See Table 10 and 11 on this page for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
5. Performance includes clean filter and wet coil.

Table 14—Fan Performance 551C 024 — Vertical Discharge Units; Standard Motor (Belt Drive)**

AIRFLOW

EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(Cfm)

0.1

0.2

0.4

0.6

0.8

1.0

(Cfm)

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

600

500

0.08

531

0.08

607

0.14

713

0.21

788

0.29

878

0.37

700

529

0.09

567

0.09

633

0.16

739

0.24

816

0.32

902

0.41

800

547

0.1

592

0.12

660

0.19

761

0.27

845

0.37

937

0.47

900

570

0.13

620

0.14

691

0.22

793

0.32

870

0.42

957

0.53

1000

599

0.15

650

0.16

717

0.26

818

0.36

894

0.47

981

0.58

551B

,C